8.2.3.2.3 Binary Output, Direct Operate, No Acknowledge, Configurable Device (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

10:56:28.359 Running procedure: 8.2.3.2.3
10:56:28.360 This procedure is enabled because the following options:
10:56:28.360 - supports.binaryOutput.commands == true
10:56:28.360 - supports.disable.binaryOutput == true
10:56:28.360 step: 1
10:56:28.360 - The DUT's binary outputs can be uninstalled or disabled through its configuration
10:56:28.360 step: 2
10:56:28.360 - Uninstall or disable every binary output point on the DUT
10:56:28.360 [PLG] All binary output status points were uninstalled
10:56:28.360 [PLG] Cycling power
10:56:28.361 step: 3
10:56:28.361 - Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:28.361 - g12v1, 2-Byte Count and Index, count: 1
10:56:28.361 - [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
10:56:28.361 --A-> Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:28.361 g12v1, 2-Byte Count and Index, count: 1
10:56:28.361 [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
10:56:28.361 --T-> fir: 1 fin: 1 seq: 0
10:56:28.361 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 26 dest: 1024 src: 1
10:56:28.361 --P-> 05 64 1A C4 00 04 01 00 EC 47
10:56:28.361 C0 C0 06 0C 01 28 01 00 00 00 03 01 64 00 00 00 CD AE
10:56:28.361 C8 00 00 00 00 78 FB
10:56:28.362 step: 4
10:56:28.362 - Verify that no link layer frames are received within 2000 ms
10:56:30.363 frame receive timeout
10:56:30.363 step: 5
10:56:30.363 - Check that no binary control point operated
10:56:31.364 [PLG] Binary output did NOT operate
10:56:31.364 Passed procedure: 8.2.3.2.3
10:56:31.364 restore
10:56:31.364 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
10:56:31.364 [PLG] All points were reinstalled
10:56:31.364 [PLG] Cycling power