8.2.6 No Control When Status Code is Non-Zero (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

10:56:32.322 Running procedure: 8.2.6
10:56:32.324 This procedure is enabled because the following options:
10:56:32.324 - supports.binaryOutput.commands == true
10:56:32.324 step: 1
10:56:32.324 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:32.324 - g12v1, 2-Byte Count and Index, count: 1
10:56:32.324 - [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 126 (NON_PARTICIPATING)
10:56:32.324 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:32.324 g12v1, 2-Byte Count and Index, count: 1
10:56:32.324 [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 126 (NON_PARTICIPATING)
10:56:32.324 --T-> fir: 1 fin: 1 seq: 0
10:56:32.324 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 26 dest: 1024 src: 1
10:56:32.324 --P-> 05 64 1A C4 00 04 01 00 EC 47
10:56:32.324 C0 C0 03 0C 01 28 01 00 00 00 03 01 64 00 00 00 FD 6B
10:56:32.324 C8 00 00 00 7E AF 79
10:56:32.325 steps: 2 to 3
10:56:32.325 - Read a single fragment response w/ sequence(0x00)
10:56:32.325 - Verify that the response echoes the select, but for its status code
10:56:32.325 - Verify that the status code isn't zero; a DUT that answers with zero passes with a warning: it complies with IEEE 1815-2012, but not with IEEE 1815-202x
10:56:32.325 - Verify that the IIN field has no error bits but IIN2.1 and IIN2.2, which are optional
10:56:32.325 - Verify that the IIN field does not contain bits IIN(FuncNotSupported)
10:56:32.326 <-P-- 05 64 1C 44 01 00 00 04 7F 9B
10:56:32.326 C0 C0 81 90 00 0C 01 28 01 00 00 00 03 01 64 00 09 60
10:56:32.326 00 00 C8 00 00 00 00 78 FB
10:56:32.326 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 28 dest: 1 src: 1024
10:56:32.326 <-T-- fir: 1 fin: 1 seq: 0
10:56:32.326 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
10:56:32.326 g12v1, 2-Byte Count and Index, count: 1
10:56:32.326 [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
10:56:32.327 Warning on the result: the DUT echoes a select whose status field isn't zero with status code 0: it complies with IEEE 1815-2012, but not with IEEE 1815-202x
10:56:32.327 Passed procedure: 8.2.6