8.22.1 Disable Double Bit Binaries (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

11:02:04.413 Running procedure: 8.22.1
11:02:04.414 step: 1
11:02:04.414 - Uninstall or disable every double-bit binary input point on the DUT
11:02:04.414 [PLG] All double-bit binary input points were uninstalled
11:02:04.414 [PLG] Cycling power
11:02:04.414 step: 2
11:02:04.414 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:02:04.414 - g4v0, All Objects
11:02:04.415 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:02:04.415 g4v0, All Objects
11:02:04.415 --T-> fir: 1 fin: 1 seq: 0
11:02:04.415 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
11:02:04.415 --P-> 05 64 0B C4 00 04 01 00 CA 8A
11:02:04.415 C0 C1 01 04 00 06 05 23
11:02:04.415 step: 3
11:02:04.415 - Read a single fragment response w/ sequence(0x01)
11:02:04.415 - Verify that the response is empty
11:02:04.415 - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown)
11:02:04.415 - Verify that the IIN field does not contain bits IIN(FuncNotSupported)
11:02:04.415 <-P-- 05 64 0A 44 01 00 00 04 67 88
11:02:04.415 C0 C1 81 90 02 CF 82
11:02:04.415 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
11:02:04.415 <-T-- fir: 1 fin: 1 seq: 0
11:02:04.415 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime, ObjectUnknown)
11:02:04.415 Passed procedure: 8.22.1
11:02:04.415 restore
11:02:04.415 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
11:02:04.415 [PLG] All points were reinstalled
11:02:04.415 [PLG] Cycling power