8.23.2.2.1 Device Does Not Support Binary Output Status Points (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

11:03:41.069 Running procedure: 8.23.2.2.1
11:03:41.070 This procedure is enabled because the following options:
11:03:41.070 - supports.binaryOutput.status == false or (supports.binaryOutput.status == true and supports.disable.binaryOutput == true)
11:03:41.070 step: 1
11:03:41.070 - Uninstall or disable every binary output point on the DUT
11:03:41.070 [PLG] All binary output status points were uninstalled
11:03:41.070 [PLG] Cycling power
11:03:41.071 step: 2
11:03:41.071 - Read g10v0 with a 8-bit (qualifier 0x00) start/stop range, 0 to 0, w/ sequence(0x01)
11:03:41.071 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:03:41.071 - g10v0, 1-Byte Start/Stop, start: 0 stop: 0
11:03:41.071 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:03:41.071 g10v0, 1-Byte Start/Stop, start: 0 stop: 0
11:03:41.071 --T-> fir: 1 fin: 1 seq: 0
11:03:41.071 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 13 dest: 1024 src: 1
11:03:41.071 --P-> 05 64 0D C4 00 04 01 00 13 E1
11:03:41.071 C0 C1 01 0A 00 00 00 00 3E BC
11:03:41.071 step: 3
11:03:41.071 - Read a single fragment response w/ sequence(0x01)
11:03:41.071 - Verify that the response is empty
11:03:41.071 - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown)
11:03:41.071 - Verify that the IIN field does not contain bits IIN(FuncNotSupported)
11:03:41.071 <-P-- 05 64 0A 44 01 00 00 04 67 88
11:03:41.071 C0 C1 81 90 02 CF 82
11:03:41.071 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
11:03:41.071 <-T-- fir: 1 fin: 1 seq: 0
11:03:41.071 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime, ObjectUnknown)
11:03:41.071 step: 4
11:03:41.071 - Read g10v0 with a 16-bit (qualifier 0x01) start/stop range, 0 to 0, w/ sequence(0x02)
11:03:41.071 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
11:03:41.071 - g10v0, 2-Byte Start/Stop, start: 0 stop: 0
11:03:41.071 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
11:03:41.071 g10v0, 2-Byte Start/Stop, start: 0 stop: 0
11:03:41.071 --T-> fir: 1 fin: 1 seq: 0
11:03:41.071 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 15 dest: 1024 src: 1
11:03:41.072 --P-> 05 64 0F C4 00 04 01 00 A4 C7
11:03:41.072 C0 C2 01 0A 00 01 00 00 00 00 35 E0
11:03:41.072 step: 5
11:03:41.072 - Read a single fragment response w/ sequence(0x02)
11:03:41.072 - Verify that the response is empty
11:03:41.072 - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown)
11:03:41.072 - Verify that the IIN field does not contain bits IIN(FuncNotSupported)
11:03:41.072 <-P-- 05 64 0A 44 01 00 00 04 67 88
11:03:41.072 C1 C2 81 90 02 88 AB
11:03:41.072 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
11:03:41.072 <-T-- fir: 1 fin: 1 seq: 1
11:03:41.072 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02 IIN(DeviceRestart, NeedTime, ObjectUnknown)
11:03:41.072 step: 6
11:03:41.072 - The binary output status points are back, if they were uninstalled
11:03:41.072 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
11:03:41.072 [PLG] All points were reinstalled
11:03:41.072 [PLG] Cycling power
11:03:41.072 Passed procedure: 8.23.2.2.1
11:03:41.072 restore
11:03:41.072 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them