8.23.2.6.1 Device Does Not Support Analog Output Status (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

11:03:43.783 Running procedure: 8.23.2.6.1
11:03:43.784 This procedure is enabled because the following options:
11:03:43.784 - supports.analogOutput.status == false or (supports.analogOutput.status == true and supports.disable.analogOutput == true)
11:03:43.784 step: 1
11:03:43.784 - Uninstall or disable every analog output point on the DUT
11:03:43.784 [PLG] All analog output status points were uninstalled
11:03:43.784 [PLG] Cycling power
11:03:43.785 step: 2
11:03:43.785 - Read g40v0 with a 8-bit (qualifier 0x00) start/stop range, 0 to 0, w/ sequence(0x01)
11:03:43.785 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:03:43.785 - g40v0, 1-Byte Start/Stop, start: 0 stop: 0
11:03:43.785 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:03:43.785 g40v0, 1-Byte Start/Stop, start: 0 stop: 0
11:03:43.785 --T-> fir: 1 fin: 1 seq: 0
11:03:43.785 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 13 dest: 1024 src: 1
11:03:43.785 --P-> 05 64 0D C4 00 04 01 00 13 E1
11:03:43.785 C0 C1 01 28 00 00 00 00 6F E2
11:03:43.785 steps: 3 to 4
11:03:43.785 - Read a single fragment response w/ sequence(0x01)
11:03:43.785 - Verify that the response is empty
11:03:43.785 - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown)
11:03:43.785 - Verify that the IIN field does not contain bits IIN(FuncNotSupported)
11:03:43.785 <-P-- 05 64 0A 44 01 00 00 04 67 88
11:03:43.785 C0 C1 81 90 02 CF 82
11:03:43.785 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
11:03:43.785 <-T-- fir: 1 fin: 1 seq: 0
11:03:43.785 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime, ObjectUnknown)
11:03:43.785 step: 5
11:03:43.785 - Read g40v0 with a 16-bit (qualifier 0x01) start/stop range, 0 to 0, w/ sequence(0x02)
11:03:43.785 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
11:03:43.785 - g40v0, 2-Byte Start/Stop, start: 0 stop: 0
11:03:43.786 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
11:03:43.786 g40v0, 2-Byte Start/Stop, start: 0 stop: 0
11:03:43.786 --T-> fir: 1 fin: 1 seq: 0
11:03:43.786 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 15 dest: 1024 src: 1
11:03:43.786 --P-> 05 64 0F C4 00 04 01 00 A4 C7
11:03:43.786 C0 C2 01 28 00 01 00 00 00 00 00 94
11:03:43.786 step: 6
11:03:43.786 - Read a single fragment response w/ sequence(0x02)
11:03:43.786 - Verify that the response is empty
11:03:43.786 - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown)
11:03:43.786 - Verify that the IIN field does not contain bits IIN(FuncNotSupported)
11:03:43.786 <-P-- 05 64 0A 44 01 00 00 04 67 88
11:03:43.786 C1 C2 81 90 02 88 AB
11:03:43.786 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
11:03:43.786 <-T-- fir: 1 fin: 1 seq: 1
11:03:43.786 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02 IIN(DeviceRestart, NeedTime, ObjectUnknown)
11:03:43.786 step: 7
11:03:43.786 - The analog output status points are back, if they were uninstalled
11:03:43.786 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
11:03:43.786 [PLG] All points were reinstalled
11:03:43.786 [PLG] Cycling power
11:03:43.786 Passed procedure: 8.23.2.6.1
11:03:43.786 restore
11:03:43.786 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them