8.4.1.2.13 Analog Output, SBO, 32-bit values (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

10:56:47.538 Running procedure: 8.4.1.2.13
10:56:47.541 This procedure is enabled because the following options:
10:56:47.541 - supports.analogOutput.commands == true
10:56:47.542 step: 1
10:56:47.542 - Use the 32-bit analog output 10
10:56:47.542 step: 2
10:56:47.542 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:47.542 - g41v1, 2-Byte Count and Index, count: 1
10:56:47.542 - [10] - value: 70000 status: 0 (SUCCESS)
10:56:47.542 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:47.542 g41v1, 2-Byte Count and Index, count: 1
10:56:47.542 [10] - value: 70000 status: 0 (SUCCESS)
10:56:47.542 --T-> fir: 1 fin: 1 seq: 0
10:56:47.542 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 20 dest: 1024 src: 1
10:56:47.542 --P-> 05 64 14 C4 00 04 01 00 E9 B6
10:56:47.542 C0 C0 03 29 01 28 01 00 0A 00 70 11 01 00 00 E2 94
10:56:47.542 steps: 3 to 4
10:56:47.542 - The DUT has a 32-bit analog output installed
10:56:47.542 step: 5
10:56:47.542 - Read a single fragment response w/ sequence(0x00)
10:56:47.542 - Verify the response contains the exact object header:
10:56:47.542 - g41v1, 2-Byte Count and Index, count: 1
10:56:47.542 - [10] - value: 70000 status: 0 (SUCCESS)
10:56:47.543 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
10:56:47.544 <-P-- 05 64 16 44 01 00 00 04 14 27
10:56:47.544 C0 C0 81 90 00 29 01 28 01 00 0A 00 70 11 01 00 A6 61
10:56:47.544 00 FF FF
10:56:47.544 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 22 dest: 1 src: 1024
10:56:47.544 <-T-- fir: 1 fin: 1 seq: 0
10:56:47.544 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
10:56:47.544 g41v1, 2-Byte Count and Index, count: 1
10:56:47.544 [10] - value: 70000 status: 0 (SUCCESS)
10:56:47.544 step: 6
10:56:47.544 - Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
10:56:47.544 - g41v1, 2-Byte Count and Index, count: 1
10:56:47.544 - [10] - value: 70000 status: 0 (SUCCESS)
10:56:47.544 --A-> Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
10:56:47.544 g41v1, 2-Byte Count and Index, count: 1
10:56:47.544 [10] - value: 70000 status: 0 (SUCCESS)
10:56:47.544 --T-> fir: 1 fin: 1 seq: 0
10:56:47.544 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 20 dest: 1024 src: 1
10:56:47.545 --P-> 05 64 14 C4 00 04 01 00 E9 B6
10:56:47.545 C0 C1 04 29 01 28 01 00 0A 00 70 11 01 00 00 CA 7A
10:56:47.545 step: 7
10:56:47.545 - Read a single fragment response w/ sequence(0x01)
10:56:47.545 - Verify the response contains the exact object header:
10:56:47.545 - g41v1, 2-Byte Count and Index, count: 1
10:56:47.545 - [10] - value: 70000 status: 0 (SUCCESS)
10:56:47.545 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
10:56:47.546 <-P-- 05 64 16 44 01 00 00 04 14 27
10:56:47.546 C1 C1 81 92 00 29 01 28 01 00 0A 00 70 11 01 00 44 FC
10:56:47.546 00 FF FF
10:56:47.546 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 22 dest: 1 src: 1024
10:56:47.546 <-T-- fir: 1 fin: 1 seq: 1
10:56:47.546 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime, Class1Events)
10:56:47.546 g41v1, 2-Byte Count and Index, count: 1
10:56:47.546 [10] - value: 70000 status: 0 (SUCCESS)
10:56:47.546 step: 8
10:56:47.546 - Check that analog control point 10 operate
10:56:47.546 [PLG] Analog output 10 did operate
10:56:47.546 Passed procedure: 8.4.1.2.13