8.4.1.2.5 Analog Output, SBO, Execute Value does not match Select Value (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

10:56:38.715 Running procedure: 8.4.1.2.5
10:56:38.716 This procedure is enabled because the following options:
10:56:38.716 - supports.analogOutput.commands == true
10:56:38.716 step: 1
10:56:38.716 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:38.716 - g41v2, 1-Byte Count and Index, count: 1
10:56:38.716 - [0] - value: 10 status: 0 (SUCCESS)
10:56:38.717 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:38.717 g41v2, 1-Byte Count and Index, count: 1
10:56:38.717 [0] - value: 10 status: 0 (SUCCESS)
10:56:38.717 --T-> fir: 1 fin: 1 seq: 0
10:56:38.717 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 16 dest: 1024 src: 1
10:56:38.717 --P-> 05 64 10 C4 00 04 01 00 87 FB
10:56:38.717 C0 C0 03 29 02 17 01 00 0A 00 00 9F B0
10:56:38.717 step: 2
10:56:38.717 - Read a single fragment response w/ sequence(0x00)
10:56:38.717 - Verify the response contains the exact object header:
10:56:38.717 - g41v2, 1-Byte Count and Index, count: 1
10:56:38.717 - [0] - value: 10 status: 0 (SUCCESS)
10:56:38.717 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
10:56:38.718 <-P-- 05 64 12 44 01 00 00 04 7A 6A
10:56:38.718 C0 C0 81 90 00 29 02 17 01 00 0A 00 00 6A 73
10:56:38.718 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 18 dest: 1 src: 1024
10:56:38.718 <-T-- fir: 1 fin: 1 seq: 0
10:56:38.718 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
10:56:38.718 g41v2, 1-Byte Count and Index, count: 1
10:56:38.718 [0] - value: 10 status: 0 (SUCCESS)
10:56:38.719 step: 3
10:56:38.719 - Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
10:56:38.719 - g41v2, 1-Byte Count and Index, count: 1
10:56:38.719 - [0] - value: 11 status: 0 (SUCCESS)
10:56:38.719 --A-> Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
10:56:38.719 g41v2, 1-Byte Count and Index, count: 1
10:56:38.719 [0] - value: 11 status: 0 (SUCCESS)
10:56:38.719 --T-> fir: 1 fin: 1 seq: 0
10:56:38.719 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 16 dest: 1024 src: 1
10:56:38.719 --P-> 05 64 10 C4 00 04 01 00 87 FB
10:56:38.719 C0 C1 04 29 02 17 01 00 0B 00 00 F0 E8
10:56:38.719 step: 4
10:56:38.719 - Read a single fragment response w/ sequence(0x01)
10:56:38.719 - Verify the response contains the exact object header:
10:56:38.719 - g41v2, 1-Byte Count and Index, count: 1
10:56:38.719 - [0] - value: 11 status: 2 (NO_SELECT)
10:56:38.719 <-P-- 05 64 12 44 01 00 00 04 7A 6A
10:56:38.719 C1 C1 81 90 00 29 02 17 01 00 0B 00 02 B2 B5
10:56:38.719 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 18 dest: 1 src: 1024
10:56:38.719 <-T-- fir: 1 fin: 1 seq: 1
10:56:38.719 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime)
10:56:38.719 g41v2, 1-Byte Count and Index, count: 1
10:56:38.719 [0] - value: 11 status: 2 (NO_SELECT)
10:56:38.719 step: 5
10:56:38.719 - Check that no analog control point operated
10:56:39.720 [PLG] Analog output did NOT operate
10:56:39.720 Passed procedure: 8.4.1.2.5