8.4.1.2.6 Analog Output, SBO, Select 0x28, Execute 0x17 (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

10:56:39.942 Running procedure: 8.4.1.2.6
10:56:39.943 This procedure is enabled because the following options:
10:56:39.943 - supports.analogOutput.commands == true
10:56:39.943 step: 1
10:56:39.943 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:39.943 - g41v2, 2-Byte Count and Index, count: 1
10:56:39.943 - [0] - value: 10 status: 0 (SUCCESS)
10:56:39.943 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:39.943 g41v2, 2-Byte Count and Index, count: 1
10:56:39.943 [0] - value: 10 status: 0 (SUCCESS)
10:56:39.943 --T-> fir: 1 fin: 1 seq: 0
10:56:39.943 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 18 dest: 1024 src: 1
10:56:39.944 --P-> 05 64 12 C4 00 04 01 00 30 DD
10:56:39.944 C0 C0 03 29 02 28 01 00 00 00 0A 00 00 40 C3
10:56:39.944 step: 2
10:56:39.944 - Read a single fragment response w/ sequence(0x00)
10:56:39.944 - Verify the response contains the exact object header:
10:56:39.944 - g41v2, 2-Byte Count and Index, count: 1
10:56:39.944 - [0] - value: 10 status: 0 (SUCCESS)
10:56:39.944 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
10:56:39.944 <-P-- 05 64 14 44 01 00 00 04 A3 01
10:56:39.944 C0 C0 81 90 00 29 02 28 01 00 00 00 0A 00 00 C1 6C
10:56:39.944 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 20 dest: 1 src: 1024
10:56:39.944 <-T-- fir: 1 fin: 1 seq: 0
10:56:39.944 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
10:56:39.944 g41v2, 2-Byte Count and Index, count: 1
10:56:39.944 [0] - value: 10 status: 0 (SUCCESS)
10:56:39.945 step: 3
10:56:39.945 - Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
10:56:39.945 - g41v2, 1-Byte Count and Index, count: 1
10:56:39.945 - [0] - value: 10 status: 0 (SUCCESS)
10:56:39.945 --A-> Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
10:56:39.945 g41v2, 1-Byte Count and Index, count: 1
10:56:39.945 [0] - value: 10 status: 0 (SUCCESS)
10:56:39.945 --T-> fir: 1 fin: 1 seq: 0
10:56:39.945 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 16 dest: 1024 src: 1
10:56:39.945 --P-> 05 64 10 C4 00 04 01 00 87 FB
10:56:39.945 C0 C1 04 29 02 17 01 00 0A 00 00 48 F1
10:56:39.945 step: 4
10:56:39.945 - Read a single fragment response w/ sequence(0x01)
10:56:39.945 - Verify the response contains the exact object header:
10:56:39.945 - g41v2, 1-Byte Count and Index, count: 1
10:56:39.945 - [0] - value: 10 status: 2 (NO_SELECT)
10:56:39.946 <-P-- 05 64 12 44 01 00 00 04 7A 6A
10:56:39.946 C1 C1 81 90 00 29 02 17 01 00 0A 00 02 0A AC
10:56:39.946 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 18 dest: 1 src: 1024
10:56:39.946 <-T-- fir: 1 fin: 1 seq: 1
10:56:39.946 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime)
10:56:39.946 g41v2, 1-Byte Count and Index, count: 1
10:56:39.946 [0] - value: 10 status: 2 (NO_SELECT)
10:56:39.946 step: 5
10:56:39.946 - Check that no analog control point operated
10:56:40.947 [PLG] Analog output did NOT operate
10:56:40.947 Passed procedure: 8.4.1.2.6