| 10:56:49.219 | Running procedure: 8.4.2.2.3 | |
| 10:56:49.220 | This procedure is enabled because the following options: | |
| 10:56:49.220 | - supports.analogOutput.commands == true | |
| 10:56:49.220 | - supports.disable.analogOutput == true | |
| 10:56:49.220 | step: 1 | |
| 10:56:49.220 | - The DUT's analog outputs can be uninstalled or disabled through its configuration | |
| 10:56:49.220 | step: 2 | |
| 10:56:49.220 | - Uninstall or disable every analog output point on the DUT | |
| 10:56:49.220 | [PLG] | All analog output status points were uninstalled |
| 10:56:49.220 | [PLG] | Cycling power |
| 10:56:49.221 | step: 3 | |
| 10:56:49.221 | - Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 | |
| 10:56:49.221 | - g41v2, 2-Byte Count and Index, count: 1 | |
| 10:56:49.221 | - [0] - value: 10 status: 0 (SUCCESS) | |
| 10:56:49.221 | --A-> | Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 |
| 10:56:49.221 | g41v2, 2-Byte Count and Index, count: 1 | |
| 10:56:49.221 | [0] - value: 10 status: 0 (SUCCESS) | |
| 10:56:49.221 | --T-> | fir: 1 fin: 1 seq: 0 |
| 10:56:49.221 | --L-> | master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 18 dest: 1024 src: 1 |
| 10:56:49.221 | --P-> | 05 64 12 C4 00 04 01 00 30 DD |
| 10:56:49.221 | C0 C0 05 29 02 28 01 00 00 00 0A 00 00 64 B4 | |
| 10:56:49.221 | step: 4 | |
| 10:56:49.221 | - Read a single fragment response w/ sequence(0x00) | |
| 10:56:49.221 | - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown) | |
| 10:56:49.222 | <-P-- | 05 64 14 44 01 00 00 04 A3 01 |
| 10:56:49.222 | C0 C0 81 90 04 29 02 28 01 00 00 00 0A 00 04 81 EF | |
| 10:56:49.222 | <-L-- | master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 20 dest: 1 src: 1024 |
| 10:56:49.222 | <-T-- | fir: 1 fin: 1 seq: 0 |
| 10:56:49.222 | <-A-- | Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime, ParamError) |
| 10:56:49.222 | g41v2, 2-Byte Count and Index, count: 1 | |
| 10:56:49.222 | [0] - value: 10 status: 4 (NOT_SUPPORTED) | |
| 10:56:49.222 | step: 5 | |
| 10:56:49.222 | - Check that no analog control point operated | |
| 10:56:50.223 | [PLG] | Analog output did NOT operate |
| 10:56:50.223 | Passed procedure: 8.4.2.2.3 | |
| 10:56:50.223 | restore | |
| 10:56:50.223 | - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them | |
| 10:56:50.223 | [PLG] | All points were reinstalled |
| 10:56:50.223 | [PLG] | Cycling power |