8.4.3.2.2 Analog Output, Direct Operate, No Acknowledge, to an Uninstalled Point (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

10:56:52.674 Running procedure: 8.4.3.2.2
10:56:52.675 This procedure is enabled because the following options:
10:56:52.675 - supports.analogOutput.commands == true
10:56:52.675 step: 1
10:56:52.675 - Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:52.675 - g41v2, 2-Byte Count and Index, count: 1
10:56:52.675 - [65535] - value: 10 status: 0 (SUCCESS)
10:56:52.675 --A-> Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:52.675 g41v2, 2-Byte Count and Index, count: 1
10:56:52.675 [65535] - value: 10 status: 0 (SUCCESS)
10:56:52.675 --T-> fir: 1 fin: 1 seq: 0
10:56:52.675 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 18 dest: 1024 src: 1
10:56:52.675 --P-> 05 64 12 C4 00 04 01 00 30 DD
10:56:52.675 C0 C0 06 29 02 28 01 00 FF FF 0A 00 00 4B 5D
10:56:52.676 step: 2
10:56:52.676 - Verify that no link layer frames are received within 2000 ms
10:56:54.678 frame receive timeout
10:56:54.678 step: 3
10:56:54.678 - Check that no analog control point operated
10:56:55.679 [PLG] Analog output did NOT operate
10:56:55.679 Passed procedure: 8.4.3.2.2