6.7.2 Test Procedure (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

05:24:21.363 Running procedure: 6.7.2
05:24:21.367 This procedure is enabled because the following options:
05:24:21.367 - supports.selfAddress == true
05:24:21.367 step: 1
05:24:21.367 - Device supports self-address
05:24:21.367 step: 2
05:24:21.367 - Enable data link self-address support
05:24:21.367 [PLG] Self address support is set to true
05:24:21.367 [PLG] Cycling power
05:24:21.368 step: 3
05:24:21.368 - Cycle power to the DUT
05:24:21.368 [PLG] Cycling power
05:24:21.370 step: 4
05:24:21.370 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 using link options: { destination == 0xFFFC }
05:24:21.370 - g60v1, All Objects
05:24:21.370 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:24:21.370 g60v1, All Objects
05:24:21.370 --T-> fir: 1 fin: 1 seq: 0
05:24:21.370 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 65532 src: 1
05:24:21.371 --P-> 05 64 0B C4 FC FF 01 00 DE 05
05:24:21.371 C0 C0 01 3C 01 06 FF 50
05:24:21.371 step: 5
05:24:21.371 - Read any number of valid responses beginning w/ sequence(0x00) and incrementing by 1 modulo 16
05:24:21.371 - Confirm each response that asks for a confirmation
05:24:21.372 <-P-- 05 64 E0 44 01 00 00 04 70 7A
05:24:21.372 C0 C0 81 90 00 01 01 01 00 00 0B 00 00 00 0A 02 97 78
05:24:21.372 01 00 00 13 00 01 01 01 01 01 01 01 01 01 01 01 96 07
05:24:21.372 01 01 01 01 01 01 01 01 01 14 02 01 00 00 09 00 26 7E
05:24:21.372 01 00 00 01 00 00 01 00 00 01 00 00 01 00 00 01 FE 85
05:24:21.372 00 00 01 00 00 01 00 00 01 00 00 01 00 00 15 02 85 CD
05:24:21.372 01 00 00 09 00 01 00 00 01 00 00 01 00 00 01 00 B6 06
05:24:21.372 00 01 00 00 01 00 00 01 00 00 01 00 00 01 00 00 9E 0F
05:24:21.373 01 00 00 1E 02 01 00 00 09 00 01 00 00 01 00 00 0A 10
05:24:21.373 01 00 00 01 00 00 01 00 00 01 00 00 01 00 00 01 FE 85
05:24:21.373 00 00 01 00 00 01 00 00 28 02 01 00 00 13 00 01 EF FE
05:24:21.373 00 00 01 00 00 01 00 00 01 00 00 01 00 00 01 00 DB 49
05:24:21.373 00 01 00 00 01 00 00 01 00 00 01 00 00 01 00 00 9E 0F
05:24:21.373 01 00 00 01 00 00 01 00 00 01 00 00 01 00 00 01 FE 85
05:24:21.373 00 00 01 00 00 01 00 00 01 00 00 61 8D
05:24:21.373 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 224 dest: 1 src: 1024
05:24:21.373 <-T-- fir: 1 fin: 1 seq: 0
05:24:21.375 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
05:24:21.375 g1v1, 2-Byte Start/Stop, start: 0 stop: 11
05:24:21.375 [0] - BooleanValue(false)
05:24:21.375 [1] - BooleanValue(false)
05:24:21.375 [2] - BooleanValue(false)
05:24:21.375 [3] - BooleanValue(false)
05:24:21.375 [4] - BooleanValue(false)
05:24:21.375 [5] - BooleanValue(false)
05:24:21.375 [6] - BooleanValue(false)
05:24:21.375 [7] - BooleanValue(false)
05:24:21.375 [8] - BooleanValue(false)
05:24:21.375 [9] - BooleanValue(false)
05:24:21.375 [10] - BooleanValue(false)
05:24:21.375 [11] - BooleanValue(false)
05:24:21.375 g10v2, 2-Byte Start/Stop, start: 0 stop: 19
05:24:21.375 [0] - flags: 0x01
05:24:21.375 [1] - flags: 0x01
05:24:21.375 [2] - flags: 0x01
05:24:21.375 [3] - flags: 0x01
05:24:21.375 [4] - flags: 0x01
05:24:21.375 [5] - flags: 0x01
05:24:21.375 [6] - flags: 0x01
05:24:21.375 [7] - flags: 0x01
05:24:21.375 [8] - flags: 0x01
05:24:21.375 [9] - flags: 0x01
05:24:21.375 [10] - flags: 0x01
05:24:21.375 [11] - flags: 0x01
05:24:21.375 [12] - flags: 0x01
05:24:21.375 [13] - flags: 0x01
05:24:21.375 [14] - flags: 0x01
05:24:21.375 [15] - flags: 0x01
05:24:21.375 [16] - flags: 0x01
05:24:21.375 [17] - flags: 0x01
05:24:21.375 [18] - flags: 0x01
05:24:21.375 [19] - flags: 0x01
05:24:21.375 g20v2, 2-Byte Start/Stop, start: 0 stop: 9
05:24:21.375 [0] - flags: 0x01 count: 0
05:24:21.375 [1] - flags: 0x01 count: 0
05:24:21.375 [2] - flags: 0x01 count: 0
05:24:21.375 [3] - flags: 0x01 count: 0
05:24:21.375 [4] - flags: 0x01 count: 0
05:24:21.375 [5] - flags: 0x01 count: 0
05:24:21.375 [6] - flags: 0x01 count: 0
05:24:21.375 [7] - flags: 0x01 count: 0
05:24:21.375 [8] - flags: 0x01 count: 0
05:24:21.375 [9] - flags: 0x01 count: 0
05:24:21.375 g21v2, 2-Byte Start/Stop, start: 0 stop: 9
05:24:21.375 [0] - flags: 0x01 count: 0
05:24:21.375 [1] - flags: 0x01 count: 0
05:24:21.375 [2] - flags: 0x01 count: 0
05:24:21.375 [3] - flags: 0x01 count: 0
05:24:21.375 [4] - flags: 0x01 count: 0
05:24:21.375 [5] - flags: 0x01 count: 0
05:24:21.375 [6] - flags: 0x01 count: 0
05:24:21.375 [7] - flags: 0x01 count: 0
05:24:21.375 [8] - flags: 0x01 count: 0
05:24:21.375 [9] - flags: 0x01 count: 0
05:24:21.375 g30v2, 2-Byte Start/Stop, start: 0 stop: 9
05:24:21.375 [0] - flags: 0x01 value: 0
05:24:21.375 [1] - flags: 0x01 value: 0
05:24:21.375 [2] - flags: 0x01 value: 0
05:24:21.375 [3] - flags: 0x01 value: 0
05:24:21.375 [4] - flags: 0x01 value: 0
05:24:21.375 [5] - flags: 0x01 value: 0
05:24:21.375 [6] - flags: 0x01 value: 0
05:24:21.375 [7] - flags: 0x01 value: 0
05:24:21.375 [8] - flags: 0x01 value: 0
05:24:21.375 [9] - flags: 0x01 value: 0
05:24:21.375 g40v2, 2-Byte Start/Stop, start: 0 stop: 19
05:24:21.375 [0] - flags: 0x01 value: 0
05:24:21.375 [1] - flags: 0x01 value: 0
05:24:21.375 [2] - flags: 0x01 value: 0
05:24:21.375 [3] - flags: 0x01 value: 0
05:24:21.375 [4] - flags: 0x01 value: 0
05:24:21.375 [5] - flags: 0x01 value: 0
05:24:21.375 [6] - flags: 0x01 value: 0
05:24:21.375 [7] - flags: 0x01 value: 0
05:24:21.375 [8] - flags: 0x01 value: 0
05:24:21.375 [9] - flags: 0x01 value: 0
05:24:21.375 [10] - flags: 0x01 value: 0
05:24:21.375 [11] - flags: 0x01 value: 0
05:24:21.375 [12] - flags: 0x01 value: 0
05:24:21.375 [13] - flags: 0x01 value: 0
05:24:21.375 [14] - flags: 0x01 value: 0
05:24:21.375 [15] - flags: 0x01 value: 0
05:24:21.375 [16] - flags: 0x01 value: 0
05:24:21.375 [17] - flags: 0x01 value: 0
05:24:21.375 [18] - flags: 0x01 value: 0
05:24:21.375 [19] - flags: 0x01 value: 0
05:24:21.375 step: 6
05:24:21.375 - Disable data link self-address support
05:24:21.375 [PLG] Self address support is set to false
05:24:21.375 [PLG] Cycling power
05:24:21.377 step: 7
05:24:21.377 - Cycle power to the DUT
05:24:21.377 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 using link options: { destination == 0xFFFC }
05:24:21.377 - g60v1, All Objects
05:24:21.377 [PLG] Cycling power
05:24:21.378 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:24:21.378 g60v1, All Objects
05:24:21.378 --T-> fir: 1 fin: 1 seq: 0
05:24:21.378 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 65532 src: 1
05:24:21.379 --P-> 05 64 0B C4 FC FF 01 00 DE 05
05:24:21.379 C0 C0 01 3C 01 06 FF 50
05:24:21.379 step: 8
05:24:21.379 - Verify that no link layer frames are received within 2000 ms
05:24:23.380 frame receive timeout
05:24:23.380 Passed procedure: 6.7.2