8.13.2.3 Device supports Binary Inputs, Configurable Device (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

05:28:02.089 Running procedure: 8.13.2.3
05:28:02.090 This procedure is enabled because the following options:
05:28:02.090 - supports.binaryInput == true
05:28:02.090 - supports.disable.binaryInput == true
05:28:02.090 step: 1
05:28:02.090 - The DUT's binary inputs can be uninstalled or disabled through its configuration
05:28:02.090 step: 2
05:28:02.090 - Uninstall or disable every binary input point on the DUT
05:28:02.090 [PLG] All binary input points were uninstalled
05:28:02.090 [PLG] Cycling power
05:28:02.091 step: 3
05:28:02.091 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:28:02.091 - g1v0, All Objects
05:28:02.091 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:28:02.091 g1v0, All Objects
05:28:02.091 --T-> fir: 1 fin: 1 seq: 0
05:28:02.092 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
05:28:02.092 --P-> 05 64 0B C4 00 04 01 00 CA 8A
05:28:02.092 C0 C1 01 01 00 06 5D 5C
05:28:02.092 step: 4
05:28:02.092 - Read a single fragment response w/ sequence(0x01)
05:28:02.092 - Verify that the response is a Null Response, or an Error Response whose only error bits are IIN(ObjectUnknown)
05:28:02.092 <-P-- 05 64 0A 44 01 00 00 04 67 88
05:28:02.092 C0 C1 81 90 02 CF 82
05:28:02.092 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
05:28:02.092 <-T-- fir: 1 fin: 1 seq: 0
05:28:02.092 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime, ObjectUnknown)
05:28:02.092 Passed procedure: 8.13.2.3
05:28:02.092 restore
05:28:02.092 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
05:28:02.093 [PLG] All points were reinstalled
05:28:02.093 [PLG] Cycling power