8.2.3.2.3 Binary Output, Direct Operate, No Acknowledge, Configurable Device (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

05:24:50.730 Running procedure: 8.2.3.2.3
05:24:50.732 This procedure is enabled because the following options:
05:24:50.732 - supports.binaryOutput.commands == true
05:24:50.732 - supports.disable.binaryOutput == true
05:24:50.732 step: 1
05:24:50.732 - The DUT's binary outputs can be uninstalled or disabled through its configuration
05:24:50.732 step: 2
05:24:50.732 - Uninstall or disable every binary output point on the DUT
05:24:50.732 [PLG] All binary output status points were uninstalled
05:24:50.732 [PLG] Cycling power
05:24:50.733 step: 3
05:24:50.733 - Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:24:50.733 - g12v1, 2-Byte Count and Index, count: 1
05:24:50.733 - [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
05:24:50.733 --A-> Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:24:50.733 g12v1, 2-Byte Count and Index, count: 1
05:24:50.733 [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
05:24:50.734 --T-> fir: 1 fin: 1 seq: 0
05:24:50.734 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 26 dest: 1024 src: 1
05:24:50.734 --P-> 05 64 1A C4 00 04 01 00 EC 47
05:24:50.734 C0 C0 06 0C 01 28 01 00 00 00 03 01 64 00 00 00 CD AE
05:24:50.734 C8 00 00 00 00 78 FB
05:24:50.734 step: 4
05:24:50.734 - Verify that no link layer frames are received within 2000 ms
05:24:52.736 frame receive timeout
05:24:52.736 step: 5
05:24:52.736 - Check that no binary control point operated
05:24:53.738 [PLG] Binary output did NOT operate
05:24:53.738 Passed procedure: 8.2.3.2.3
05:24:53.738 restore
05:24:53.738 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
05:24:53.738 [PLG] All points were reinstalled
05:24:53.738 [PLG] Cycling power