8.21.2.2 Device supports Double-bit Inputs, Configurable Device (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

05:29:57.834 Running procedure: 8.21.2.2
05:29:57.835 This procedure is enabled because the following options:
05:29:57.835 - supports.doubleBitInput == true
05:29:57.835 - supports.disable.doubleBitInput == true
05:29:57.835 step: 1
05:29:57.835 - The DUT's double-bit inputs can be uninstalled or disabled through its configuration
05:29:57.835 step: 2
05:29:57.835 - Uninstall or disable every double-bit binary input point on the DUT
05:29:57.835 [PLG] All double-bit binary input points were uninstalled
05:29:57.835 [PLG] Cycling power
05:29:57.837 step: 3
05:29:57.837 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:29:57.837 - g3v0, All Objects
05:29:57.837 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:29:57.837 g3v0, All Objects
05:29:57.837 --T-> fir: 1 fin: 1 seq: 0
05:29:57.837 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
05:29:57.837 --P-> 05 64 0B C4 00 04 01 00 CA 8A
05:29:57.837 C0 C0 01 03 00 06 2B 4C
05:29:57.837 step: 4
05:29:57.837 - Read a single fragment response w/ sequence(0x00)
05:29:57.837 - Verify that the response is a Null Response, or an Error Response whose only error bits are IIN(ObjectUnknown)
05:29:57.837 <-P-- 05 64 0A 44 01 00 00 04 67 88
05:29:57.837 C0 C0 81 90 02 27 40
05:29:57.837 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
05:29:57.837 <-T-- fir: 1 fin: 1 seq: 0
05:29:57.838 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime, ObjectUnknown)
05:29:57.838 Passed procedure: 8.21.2.2
05:29:57.838 restore
05:29:57.838 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
05:29:57.838 [PLG] All points were reinstalled
05:29:57.838 [PLG] Cycling power