8.4.1.2.3 Analog Output, SBO, to Uninstalled Point (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

05:24:55.400 Running procedure: 8.4.1.2.3
05:24:55.401 This procedure is enabled because the following options:
05:24:55.401 - supports.analogOutput.commands == true
05:24:55.401 step: 1
05:24:55.402 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:24:55.402 - g41v2, 2-Byte Count and Index, count: 1
05:24:55.402 - [65535] - value: 10 status: 0 (SUCCESS)
05:24:55.402 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:24:55.402 g41v2, 2-Byte Count and Index, count: 1
05:24:55.402 [65535] - value: 10 status: 0 (SUCCESS)
05:24:55.402 --T-> fir: 1 fin: 1 seq: 0
05:24:55.402 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 18 dest: 1024 src: 1
05:24:55.402 --P-> 05 64 12 C4 00 04 01 00 30 DD
05:24:55.402 C0 C0 03 29 02 28 01 00 FF FF 0A 00 00 FD 11
05:24:55.402 step: 2
05:24:55.402 - Read a single fragment response w/ sequence(0x00)
05:24:55.402 - Verify that the IIN field contains IIN(ParamError)
05:24:55.402 - Verify the response contains the exact object header:
05:24:55.402 - g41v2, 2-Byte Count and Index, count: 1
05:24:55.402 - [65535] - value: 10 status: 4 (NOT_SUPPORTED)
05:24:55.403 <-P-- 05 64 14 44 01 00 00 04 A3 01
05:24:55.403 C0 C0 81 90 04 29 02 28 01 00 FF FF 0A 00 04 3C 3D
05:24:55.403 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 20 dest: 1 src: 1024
05:24:55.403 <-T-- fir: 1 fin: 1 seq: 0
05:24:55.403 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime, ParamError)
05:24:55.403 g41v2, 2-Byte Count and Index, count: 1
05:24:55.403 [65535] - value: 10 status: 4 (NOT_SUPPORTED)
05:24:55.403 step: 3
05:24:55.403 - Check that no analog control point operated
05:24:56.405 [PLG] Analog output did NOT operate
05:24:56.405 Passed procedure: 8.4.1.2.3