8.4.1.2.5 Analog Output, SBO, Execute Value does not match Select Value (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

05:25:00.861 Running procedure: 8.4.1.2.5
05:25:00.863 This procedure is enabled because the following options:
05:25:00.863 - supports.analogOutput.commands == true
05:25:00.863 step: 1
05:25:00.863 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:00.863 - g41v2, 1-Byte Count and Index, count: 1
05:25:00.863 - [0] - value: 10 status: 0 (SUCCESS)
05:25:00.864 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:00.864 g41v2, 1-Byte Count and Index, count: 1
05:25:00.864 [0] - value: 10 status: 0 (SUCCESS)
05:25:00.864 --T-> fir: 1 fin: 1 seq: 0
05:25:00.864 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 16 dest: 1024 src: 1
05:25:00.864 --P-> 05 64 10 C4 00 04 01 00 87 FB
05:25:00.864 C0 C0 03 29 02 17 01 00 0A 00 00 9F B0
05:25:00.864 step: 2
05:25:00.864 - Read a single fragment response w/ sequence(0x00)
05:25:00.864 - Verify the response contains the exact object header:
05:25:00.864 - g41v2, 1-Byte Count and Index, count: 1
05:25:00.864 - [0] - value: 10 status: 0 (SUCCESS)
05:25:00.864 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
05:25:00.865 <-P-- 05 64 12 44 01 00 00 04 7A 6A
05:25:00.865 C0 C0 81 90 00 29 02 17 01 00 0A 00 00 6A 73
05:25:00.865 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 18 dest: 1 src: 1024
05:25:00.865 <-T-- fir: 1 fin: 1 seq: 0
05:25:00.865 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
05:25:00.865 g41v2, 1-Byte Count and Index, count: 1
05:25:00.865 [0] - value: 10 status: 0 (SUCCESS)
05:25:00.865 step: 3
05:25:00.865 - Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:25:00.865 - g41v2, 1-Byte Count and Index, count: 1
05:25:00.865 - [0] - value: 11 status: 0 (SUCCESS)
05:25:00.865 --A-> Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:25:00.865 g41v2, 1-Byte Count and Index, count: 1
05:25:00.865 [0] - value: 11 status: 0 (SUCCESS)
05:25:00.866 --T-> fir: 1 fin: 1 seq: 0
05:25:00.866 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 16 dest: 1024 src: 1
05:25:00.866 --P-> 05 64 10 C4 00 04 01 00 87 FB
05:25:00.866 C0 C1 04 29 02 17 01 00 0B 00 00 F0 E8
05:25:00.866 step: 4
05:25:00.866 - Read a single fragment response w/ sequence(0x01)
05:25:00.866 - Verify the response contains the exact object header:
05:25:00.866 - g41v2, 1-Byte Count and Index, count: 1
05:25:00.866 - [0] - value: 11 status: 2 (NO_SELECT)
05:25:00.866 <-P-- 05 64 12 44 01 00 00 04 7A 6A
05:25:00.866 C1 C1 81 90 00 29 02 17 01 00 0B 00 02 B2 B5
05:25:00.866 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 18 dest: 1 src: 1024
05:25:00.866 <-T-- fir: 1 fin: 1 seq: 1
05:25:00.866 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime)
05:25:00.866 g41v2, 1-Byte Count and Index, count: 1
05:25:00.866 [0] - value: 11 status: 2 (NO_SELECT)
05:25:00.866 step: 5
05:25:00.866 - Check that no analog control point operated
05:25:01.868 [PLG] Analog output did NOT operate
05:25:01.868 Passed procedure: 8.4.1.2.5