8.4.1.2.6 Analog Output, SBO, Select 0x28, Execute 0x17 (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

05:25:02.089 Running procedure: 8.4.1.2.6
05:25:02.090 This procedure is enabled because the following options:
05:25:02.090 - supports.analogOutput.commands == true
05:25:02.091 step: 1
05:25:02.091 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:02.091 - g41v2, 2-Byte Count and Index, count: 1
05:25:02.091 - [0] - value: 10 status: 0 (SUCCESS)
05:25:02.091 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:02.091 g41v2, 2-Byte Count and Index, count: 1
05:25:02.091 [0] - value: 10 status: 0 (SUCCESS)
05:25:02.091 --T-> fir: 1 fin: 1 seq: 0
05:25:02.091 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 18 dest: 1024 src: 1
05:25:02.091 --P-> 05 64 12 C4 00 04 01 00 30 DD
05:25:02.091 C0 C0 03 29 02 28 01 00 00 00 0A 00 00 40 C3
05:25:02.092 step: 2
05:25:02.092 - Read a single fragment response w/ sequence(0x00)
05:25:02.092 - Verify the response contains the exact object header:
05:25:02.092 - g41v2, 2-Byte Count and Index, count: 1
05:25:02.092 - [0] - value: 10 status: 0 (SUCCESS)
05:25:02.092 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
05:25:02.092 <-P-- 05 64 14 44 01 00 00 04 A3 01
05:25:02.092 C0 C0 81 90 00 29 02 28 01 00 00 00 0A 00 00 C1 6C
05:25:02.092 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 20 dest: 1 src: 1024
05:25:02.092 <-T-- fir: 1 fin: 1 seq: 0
05:25:02.092 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
05:25:02.092 g41v2, 2-Byte Count and Index, count: 1
05:25:02.092 [0] - value: 10 status: 0 (SUCCESS)
05:25:02.092 step: 3
05:25:02.092 - Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:25:02.092 - g41v2, 1-Byte Count and Index, count: 1
05:25:02.092 - [0] - value: 10 status: 0 (SUCCESS)
05:25:02.093 --A-> Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:25:02.093 g41v2, 1-Byte Count and Index, count: 1
05:25:02.093 [0] - value: 10 status: 0 (SUCCESS)
05:25:02.093 --T-> fir: 1 fin: 1 seq: 0
05:25:02.093 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 16 dest: 1024 src: 1
05:25:02.093 --P-> 05 64 10 C4 00 04 01 00 87 FB
05:25:02.093 C0 C1 04 29 02 17 01 00 0A 00 00 48 F1
05:25:02.093 step: 4
05:25:02.093 - Read a single fragment response w/ sequence(0x01)
05:25:02.093 - Verify the response contains the exact object header:
05:25:02.093 - g41v2, 1-Byte Count and Index, count: 1
05:25:02.093 - [0] - value: 10 status: 2 (NO_SELECT)
05:25:02.093 <-P-- 05 64 12 44 01 00 00 04 7A 6A
05:25:02.093 C1 C1 81 90 00 29 02 17 01 00 0A 00 02 0A AC
05:25:02.093 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 18 dest: 1 src: 1024
05:25:02.093 <-T-- fir: 1 fin: 1 seq: 1
05:25:02.094 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime)
05:25:02.094 g41v2, 1-Byte Count and Index, count: 1
05:25:02.094 [0] - value: 10 status: 2 (NO_SELECT)
05:25:02.094 step: 5
05:25:02.094 - Check that no analog control point operated
05:25:03.095 [PLG] Analog output did NOT operate
05:25:03.095 Passed procedure: 8.4.1.2.6