8.4.2.2.3 Analog Output, Direct Operate, Configurable Device (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

05:25:11.178 Running procedure: 8.4.2.2.3
05:25:11.179 This procedure is enabled because the following options:
05:25:11.179 - supports.analogOutput.commands == true
05:25:11.179 - supports.disable.analogOutput == true
05:25:11.179 step: 1
05:25:11.179 - The DUT's analog outputs can be uninstalled or disabled through its configuration
05:25:11.179 step: 2
05:25:11.179 - Uninstall or disable every analog output point on the DUT
05:25:11.179 [PLG] All analog output status points were uninstalled
05:25:11.179 [PLG] Cycling power
05:25:11.180 step: 3
05:25:11.180 - Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:11.180 - g41v2, 2-Byte Count and Index, count: 1
05:25:11.180 - [0] - value: 10 status: 0 (SUCCESS)
05:25:11.181 --A-> Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:11.181 g41v2, 2-Byte Count and Index, count: 1
05:25:11.181 [0] - value: 10 status: 0 (SUCCESS)
05:25:11.181 --T-> fir: 1 fin: 1 seq: 0
05:25:11.181 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 18 dest: 1024 src: 1
05:25:11.181 --P-> 05 64 12 C4 00 04 01 00 30 DD
05:25:11.181 C0 C0 05 29 02 28 01 00 00 00 0A 00 00 64 B4
05:25:11.181 step: 4
05:25:11.181 - Read a single fragment response w/ sequence(0x00)
05:25:11.181 - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown)
05:25:11.182 <-P-- 05 64 14 44 01 00 00 04 A3 01
05:25:11.182 C0 C0 81 90 04 29 02 28 01 00 00 00 0A 00 04 81 EF
05:25:11.183 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 20 dest: 1 src: 1024
05:25:11.183 <-T-- fir: 1 fin: 1 seq: 0
05:25:11.183 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime, ParamError)
05:25:11.183 g41v2, 2-Byte Count and Index, count: 1
05:25:11.183 [0] - value: 10 status: 4 (NOT_SUPPORTED)
05:25:11.183 step: 5
05:25:11.183 - Check that no analog control point operated
05:25:12.184 [PLG] Analog output did NOT operate
05:25:12.184 Passed procedure: 8.4.2.2.3
05:25:12.184 restore
05:25:12.184 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
05:25:12.184 [PLG] All points were reinstalled
05:25:12.184 [PLG] Cycling power