8.4.3.2.2 Analog Output, Direct Operate, No Acknowledge, to an Uninstalled Point (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

05:25:14.633 Running procedure: 8.4.3.2.2
05:25:14.634 This procedure is enabled because the following options:
05:25:14.634 - supports.analogOutput.commands == true
05:25:14.634 step: 1
05:25:14.634 - Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:14.634 - g41v2, 2-Byte Count and Index, count: 1
05:25:14.634 - [65535] - value: 10 status: 0 (SUCCESS)
05:25:14.635 --A-> Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:14.635 g41v2, 2-Byte Count and Index, count: 1
05:25:14.635 [65535] - value: 10 status: 0 (SUCCESS)
05:25:14.635 --T-> fir: 1 fin: 1 seq: 0
05:25:14.635 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 18 dest: 1024 src: 1
05:25:14.635 --P-> 05 64 12 C4 00 04 01 00 30 DD
05:25:14.635 C0 C0 06 29 02 28 01 00 FF FF 0A 00 00 4B 5D
05:25:14.635 step: 2
05:25:14.635 - Verify that no link layer frames are received within 2000 ms
05:25:16.637 frame receive timeout
05:25:16.637 step: 3
05:25:16.637 - Check that no analog control point operated
05:25:17.639 [PLG] Analog output did NOT operate
05:25:17.639 Passed procedure: 8.4.3.2.2