8.6.5.3 Test Procedure (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

05:25:48.584 Running procedure: 8.6.5.3
05:25:48.586 This procedure is enabled because the following options:
05:25:48.586 - supports.binaryOutput.commands == true or supports.analogOutput.commands == true
05:25:48.586 step: 1
05:25:48.586 - Tell a manual tester: Watch binary output 0: it should operate once after the broadcast in step 1. You'll be asked what you saw after the steps. Get ready, then press ENTER.
05:25:48.586 - Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 using link options: { destination == 0xFFFF }
05:25:48.586 - g12v1, 1-Byte Count and Index, count: 1
05:25:48.586 - [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
05:25:48.587 --A-> Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:48.587 g12v1, 1-Byte Count and Index, count: 1
05:25:48.587 [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
05:25:48.587 --T-> fir: 1 fin: 1 seq: 0
05:25:48.587 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 24 dest: 65535 src: 1
05:25:48.587 --P-> 05 64 18 C4 FF FF 01 00 0E E4
05:25:48.587 C0 C0 06 0C 01 17 01 00 03 01 64 00 00 00 C8 00 CD D4
05:25:48.587 00 00 00 FF FF
05:25:48.587 step: 2
05:25:48.587 - Check that binary control point 0 operate
05:25:48.687 [PLG] Binary output 0 did operate
05:25:48.687 steps: 3 to 4
05:25:48.687 - Verify that no link layer frames are received within 2000 ms
05:25:50.689 frame receive timeout
05:25:50.689 step: 5
05:25:50.689 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
05:25:50.689 - g60v2, All Objects
05:25:50.689 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
05:25:50.689 g60v2, All Objects
05:25:50.689 --T-> fir: 1 fin: 1 seq: 0
05:25:50.689 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
05:25:50.689 --P-> 05 64 0B C4 00 04 01 00 CA 8A
05:25:50.689 C0 C2 01 3C 02 06 58 A6
05:25:50.690 steps: 6 to 7
05:25:50.690 - Read any number of valid responses beginning w/ sequence(0x02) and incrementing by 1 modulo 16
05:25:50.690 - Verify that each fragment followed by another, or carrying events, asks for an application layer confirmation.
05:25:50.690 - Verify that the IIN field contains IIN(Broadcast)
05:25:50.690 - Confirm each response that asks for a confirmation
05:25:50.690 <-P-- 05 64 0A 44 01 00 00 04 67 88
05:25:50.690 C0 C2 81 91 00 7C 4F
05:25:50.690 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
05:25:50.690 <-T-- fir: 1 fin: 1 seq: 0
05:25:50.690 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02 IIN(DeviceRestart, NeedTime, Broadcast)
05:25:50.690 step: 8
05:25:50.690 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x03
05:25:50.690 - g60v2, All Objects
05:25:50.690 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x03
05:25:50.690 g60v2, All Objects
05:25:50.690 --T-> fir: 1 fin: 1 seq: 0
05:25:50.690 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
05:25:50.690 --P-> 05 64 0B C4 00 04 01 00 CA 8A
05:25:50.690 C0 C3 01 3C 02 06 5E 85
05:25:50.691 step: 9
05:25:50.691 - Read a single fragment response w/ sequence(0x03)
05:25:50.691 - Verify that the response is empty
05:25:50.691 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
05:25:50.691 - Verify that the IIN field does not contain bits IIN(Broadcast)
05:25:50.691 <-P-- 05 64 0A 44 01 00 00 04 67 88
05:25:50.691 C1 C3 81 90 00 DC 05
05:25:50.691 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
05:25:50.691 <-T-- fir: 1 fin: 1 seq: 1
05:25:50.691 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x03 IIN(DeviceRestart, NeedTime)
05:25:50.691 Passed procedure: 8.6.5.3