8.2.3.2.2 Binary Output, Direct Operate, No Acknowledge, to an Uninstalled Point (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

05:24:37.634 Running procedure: 8.2.3.2.2
05:24:37.636 This procedure is enabled because the following options:
05:24:37.636 - supports.binaryOutput.commands == true
05:24:37.636 step: 1
05:24:37.636 - Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:24:37.636 - g12v1, 2-Byte Count and Index, count: 1
05:24:37.636 - [65535] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
05:24:37.636 --A-> Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:24:37.636 g12v1, 2-Byte Count and Index, count: 1
05:24:37.636 [65535] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
05:24:37.636 --T-> fir: 1 fin: 1 seq: 0
05:24:37.636 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 26 dest: 1024 src: 1
05:24:37.637 --P-> 05 64 1A C4 00 04 01 00 EC 47
05:24:37.637 C0 C0 06 0C 01 28 01 00 FF FF 03 01 64 00 00 00 49 0B
05:24:37.637 C8 00 00 00 00 78 FB
05:24:37.637 step: 2
05:24:37.637 - Verify that no link layer frames are received within 2000 ms
05:24:39.639 frame receive timeout
05:24:39.639 step: 3
05:24:39.639 - Check that no binary control point operated
05:24:40.640 [PLG] Binary output did NOT operate
05:24:40.640 Passed procedure: 8.2.3.2.2