8.21d Device supports Double-bit Inputs, Configurable Device (as 8.13.2d) (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

05:30:17.113 Running procedure: 8.21d
05:30:17.114 This procedure is enabled because the following options:
05:30:17.114 - supports.doubleBitInput == true
05:30:17.114 - supports.disable.doubleBitInput == true
05:30:17.114 - supports.doubleBitInputReads == true
05:30:17.114 step: 1
05:30:17.114 - The DUT's double-bit inputs can be uninstalled or disabled through its configuration
05:30:17.114 step: 2
05:30:17.114 - Uninstall or disable every double-bit binary input point on the DUT
05:30:17.114 [PLG] All double-bit binary input points were uninstalled
05:30:17.114 [PLG] Cycling power
05:30:17.115 step: 3
05:30:17.115 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:30:17.115 - g3v0, All Objects
05:30:17.116 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:30:17.116 g3v0, All Objects
05:30:17.116 --T-> fir: 1 fin: 1 seq: 0
05:30:17.116 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
05:30:17.116 --P-> 05 64 0B C4 00 04 01 00 CA 8A
05:30:17.116 C0 C0 01 03 00 06 2B 4C
05:30:17.116 step: 4
05:30:17.116 - Read a single fragment response w/ sequence(0x00)
05:30:17.116 - Verify that the response is empty
05:30:17.116 - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown)
05:30:17.116 - Verify that the IIN field does not contain bits IIN(FuncNotSupported)
05:30:17.117 <-P-- 05 64 0A 44 01 00 00 04 67 88
05:30:17.117 C0 C0 81 90 02 27 40
05:30:17.117 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
05:30:17.117 <-T-- fir: 1 fin: 1 seq: 0
05:30:17.117 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime, ObjectUnknown)
05:30:17.117 Passed procedure: 8.21d
05:30:17.117 restore
05:30:17.117 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
05:30:17.117 [PLG] All points were reinstalled
05:30:17.117 [PLG] Cycling power