8.22.1 Disable Double Bit Binaries (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

05:30:17.341 Running procedure: 8.22.1
05:30:17.342 step: 1
05:30:17.342 - Uninstall or disable every double-bit binary input point on the DUT
05:30:17.342 [PLG] All double-bit binary input points were uninstalled
05:30:17.342 [PLG] Cycling power
05:30:17.343 step: 2
05:30:17.343 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:30:17.343 - g4v0, All Objects
05:30:17.343 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:30:17.343 g4v0, All Objects
05:30:17.343 --T-> fir: 1 fin: 1 seq: 0
05:30:17.343 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
05:30:17.343 --P-> 05 64 0B C4 00 04 01 00 CA 8A
05:30:17.343 C0 C1 01 04 00 06 05 23
05:30:17.343 step: 3
05:30:17.343 - Read a single fragment response w/ sequence(0x01)
05:30:17.343 - Verify that the response is empty
05:30:17.343 - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown)
05:30:17.343 - Verify that the IIN field does not contain bits IIN(FuncNotSupported)
05:30:17.344 <-P-- 05 64 0A 44 01 00 00 04 67 88
05:30:17.344 C0 C1 81 90 02 CF 82
05:30:17.344 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
05:30:17.344 <-T-- fir: 1 fin: 1 seq: 0
05:30:17.344 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime, ObjectUnknown)
05:30:17.344 Passed procedure: 8.22.1
05:30:17.344 restore
05:30:17.344 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
05:30:17.344 [PLG] All points were reinstalled
05:30:17.344 [PLG] Cycling power