8.23.2.6.1 Device Does Not Support Analog Output Status (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

05:31:56.775 Running procedure: 8.23.2.6.1
05:31:56.776 This procedure is enabled because the following options:
05:31:56.776 - supports.analogOutput.status == false or (supports.analogOutput.status == true and supports.disable.analogOutput == true)
05:31:56.776 step: 1
05:31:56.776 - Uninstall or disable every analog output point on the DUT
05:31:56.776 [PLG] All analog output status points were uninstalled
05:31:56.776 [PLG] Cycling power
05:31:56.777 step: 2
05:31:56.777 - Read g40v0 with a 8-bit (qualifier 0x00) start/stop range, 0 to 0, w/ sequence(0x01)
05:31:56.777 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:31:56.777 - g40v0, 1-Byte Start/Stop, start: 0 stop: 0
05:31:56.777 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:31:56.777 g40v0, 1-Byte Start/Stop, start: 0 stop: 0
05:31:56.777 --T-> fir: 1 fin: 1 seq: 0
05:31:56.777 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 13 dest: 1024 src: 1
05:31:56.777 --P-> 05 64 0D C4 00 04 01 00 13 E1
05:31:56.777 C0 C1 01 28 00 00 00 00 6F E2
05:31:56.777 steps: 3 to 4
05:31:56.777 - Read a single fragment response w/ sequence(0x01)
05:31:56.777 - Verify that the response is empty
05:31:56.777 - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown)
05:31:56.777 - Verify that the IIN field does not contain bits IIN(FuncNotSupported)
05:31:56.778 <-P-- 05 64 0A 44 01 00 00 04 67 88
05:31:56.778 C0 C1 81 90 02 CF 82
05:31:56.778 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
05:31:56.778 <-T-- fir: 1 fin: 1 seq: 0
05:31:56.778 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime, ObjectUnknown)
05:31:56.778 step: 5
05:31:56.778 - Read g40v0 with a 16-bit (qualifier 0x01) start/stop range, 0 to 0, w/ sequence(0x02)
05:31:56.778 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
05:31:56.778 - g40v0, 2-Byte Start/Stop, start: 0 stop: 0
05:31:56.778 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
05:31:56.778 g40v0, 2-Byte Start/Stop, start: 0 stop: 0
05:31:56.778 --T-> fir: 1 fin: 1 seq: 0
05:31:56.778 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 15 dest: 1024 src: 1
05:31:56.778 --P-> 05 64 0F C4 00 04 01 00 A4 C7
05:31:56.778 C0 C2 01 28 00 01 00 00 00 00 00 94
05:31:56.778 step: 6
05:31:56.778 - Read a single fragment response w/ sequence(0x02)
05:31:56.778 - Verify that the response is empty
05:31:56.778 - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown)
05:31:56.778 - Verify that the IIN field does not contain bits IIN(FuncNotSupported)
05:31:56.778 <-P-- 05 64 0A 44 01 00 00 04 67 88
05:31:56.778 C1 C2 81 90 02 88 AB
05:31:56.778 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
05:31:56.778 <-T-- fir: 1 fin: 1 seq: 1
05:31:56.778 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02 IIN(DeviceRestart, NeedTime, ObjectUnknown)
05:31:56.779 step: 7
05:31:56.779 - The analog output status points are back, if they were uninstalled
05:31:56.779 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
05:31:56.779 [PLG] All points were reinstalled
05:31:56.779 [PLG] Cycling power
05:31:56.779 Passed procedure: 8.23.2.6.1
05:31:56.779 restore
05:31:56.779 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them