8.4.1.2.13 Analog Output, SBO, 32-bit values (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

05:25:00.095 Running procedure: 8.4.1.2.13
05:25:00.099 This procedure is enabled because the following options:
05:25:00.099 - supports.analogOutput.commands == true
05:25:00.099 step: 1
05:25:00.099 - Use the 32-bit analog output 10
05:25:00.099 step: 2
05:25:00.099 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:00.099 - g41v1, 2-Byte Count and Index, count: 1
05:25:00.099 - [10] - value: 70000 status: 0 (SUCCESS)
05:25:00.100 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:00.100 g41v1, 2-Byte Count and Index, count: 1
05:25:00.100 [10] - value: 70000 status: 0 (SUCCESS)
05:25:00.100 --T-> fir: 1 fin: 1 seq: 0
05:25:00.100 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 20 dest: 1024 src: 1
05:25:00.100 --P-> 05 64 14 C4 00 04 01 00 E9 B6
05:25:00.100 C0 C0 03 29 01 28 01 00 0A 00 70 11 01 00 00 E2 94
05:25:00.100 steps: 3 to 4
05:25:00.100 - The DUT has a 32-bit analog output installed
05:25:00.100 step: 5
05:25:00.100 - Read a single fragment response w/ sequence(0x00)
05:25:00.100 - Verify the response contains the exact object header:
05:25:00.100 - g41v1, 2-Byte Count and Index, count: 1
05:25:00.100 - [10] - value: 70000 status: 0 (SUCCESS)
05:25:00.100 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
05:25:00.101 <-P-- 05 64 16 44 01 00 00 04 14 27
05:25:00.101 C0 C0 81 90 00 29 01 28 01 00 0A 00 70 11 01 00 A6 61
05:25:00.101 00 FF FF
05:25:00.101 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 22 dest: 1 src: 1024
05:25:00.101 <-T-- fir: 1 fin: 1 seq: 0
05:25:00.101 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
05:25:00.101 g41v1, 2-Byte Count and Index, count: 1
05:25:00.101 [10] - value: 70000 status: 0 (SUCCESS)
05:25:00.101 step: 6
05:25:00.101 - Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:25:00.101 - g41v1, 2-Byte Count and Index, count: 1
05:25:00.101 - [10] - value: 70000 status: 0 (SUCCESS)
05:25:00.101 --A-> Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:25:00.101 g41v1, 2-Byte Count and Index, count: 1
05:25:00.101 [10] - value: 70000 status: 0 (SUCCESS)
05:25:00.101 --T-> fir: 1 fin: 1 seq: 0
05:25:00.102 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 20 dest: 1024 src: 1
05:25:00.102 --P-> 05 64 14 C4 00 04 01 00 E9 B6
05:25:00.102 C0 C1 04 29 01 28 01 00 0A 00 70 11 01 00 00 CA 7A
05:25:00.102 step: 7
05:25:00.102 - Read a single fragment response w/ sequence(0x01)
05:25:00.102 - Verify the response contains the exact object header:
05:25:00.102 - g41v1, 2-Byte Count and Index, count: 1
05:25:00.102 - [10] - value: 70000 status: 0 (SUCCESS)
05:25:00.102 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
05:25:00.102 <-P-- 05 64 16 44 01 00 00 04 14 27
05:25:00.102 C1 C1 81 92 00 29 01 28 01 00 0A 00 70 11 01 00 44 FC
05:25:00.102 00 FF FF
05:25:00.102 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 22 dest: 1 src: 1024
05:25:00.102 <-T-- fir: 1 fin: 1 seq: 1
05:25:00.102 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime, Class1Events)
05:25:00.102 g41v1, 2-Byte Count and Index, count: 1
05:25:00.102 [10] - value: 70000 status: 0 (SUCCESS)
05:25:00.103 step: 8
05:25:00.103 - Check that analog control point 10 operate
05:25:00.103 [PLG] Analog output 10 did operate
05:25:00.103 Passed procedure: 8.4.1.2.13