8.4.1.2.4 Analog Output, SBO, Execute Issued After Time-out (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

05:24:47.016 Running procedure: 8.4.1.2.4
05:24:47.018 This procedure is enabled because the following options:
05:24:47.018 - supports.analogOutput.commands == true
05:24:47.018 step: 1
05:24:47.018 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:24:47.018 - g41v2, 1-Byte Count and Index, count: 1
05:24:47.018 - [0] - value: 10 status: 0 (SUCCESS)
05:24:47.018 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:24:47.018 g41v2, 1-Byte Count and Index, count: 1
05:24:47.018 [0] - value: 10 status: 0 (SUCCESS)
05:24:47.018 --T-> fir: 1 fin: 1 seq: 0
05:24:47.018 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 16 dest: 1024 src: 1
05:24:47.018 --P-> 05 64 10 C4 00 04 01 00 87 FB
05:24:47.018 C0 C0 03 29 02 17 01 00 0A 00 00 9F B0
05:24:47.019 step: 2
05:24:47.019 - Read a single fragment response w/ sequence(0x00)
05:24:47.019 - Verify the response contains the exact object header:
05:24:47.019 - g41v2, 1-Byte Count and Index, count: 1
05:24:47.019 - [0] - value: 10 status: 0 (SUCCESS)
05:24:47.019 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
05:24:47.019 <-P-- 05 64 12 44 01 00 00 04 7A 6A
05:24:47.019 C0 C0 81 90 00 29 02 17 01 00 0A 00 00 6A 73
05:24:47.019 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 18 dest: 1 src: 1024
05:24:47.019 <-T-- fir: 1 fin: 1 seq: 0
05:24:47.019 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
05:24:47.019 g41v2, 1-Byte Count and Index, count: 1
05:24:47.019 [0] - value: 10 status: 0 (SUCCESS)
05:24:47.020 step: 3
05:24:47.020 - Wait for 3000 milliseconds
05:24:50.020 step: 4
05:24:50.020 - Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:24:50.020 - g41v2, 1-Byte Count and Index, count: 1
05:24:50.020 - [0] - value: 10 status: 0 (SUCCESS)
05:24:50.020 - Read a single fragment response w/ sequence(0x01)
05:24:50.020 - Verify the response contains the exact object header:
05:24:50.020 - g41v2, 1-Byte Count and Index, count: 1
05:24:50.020 - [0] - value: 10 status: 1 (TIMEOUT)
05:24:50.020 --A-> Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:24:50.020 g41v2, 1-Byte Count and Index, count: 1
05:24:50.020 [0] - value: 10 status: 0 (SUCCESS)
05:24:50.020 --T-> fir: 1 fin: 1 seq: 0
05:24:50.020 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 16 dest: 1024 src: 1
05:24:50.021 --P-> 05 64 10 C4 00 04 01 00 87 FB
05:24:50.021 C0 C1 04 29 02 17 01 00 0A 00 00 48 F1
05:24:50.021 <-P-- 05 64 12 44 01 00 00 04 7A 6A
05:24:50.021 C1 C1 81 90 00 29 02 17 01 00 0A 00 01 E8 F6
05:24:50.021 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 18 dest: 1 src: 1024
05:24:50.021 <-T-- fir: 1 fin: 1 seq: 1
05:24:50.022 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime)
05:24:50.022 g41v2, 1-Byte Count and Index, count: 1
05:24:50.022 [0] - value: 10 status: 1 (TIMEOUT)
05:24:50.022 step: 5
05:24:50.022 - Check that no analog control point operated
05:24:51.023 [PLG] Analog output did NOT operate
05:24:51.023 Passed procedure: 8.4.1.2.4