8.4.3.2.1 Analog Output, Direct Operate, No Acknowledge (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

05:25:03.008 Running procedure: 8.4.3.2.1
05:25:03.009 step: 1
05:25:03.009 - Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:03.009 - g41v2, 1-Byte Count and Index, count: 1
05:25:03.009 - [0] - value: 10 status: 0 (SUCCESS)
05:25:03.010 --A-> Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:03.010 g41v2, 1-Byte Count and Index, count: 1
05:25:03.010 [0] - value: 10 status: 0 (SUCCESS)
05:25:03.010 --T-> fir: 1 fin: 1 seq: 0
05:25:03.010 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 16 dest: 1024 src: 1
05:25:03.010 --P-> 05 64 10 C4 00 04 01 00 87 FB
05:25:03.010 C0 C0 06 29 02 17 01 00 0A 00 00 D1 C2
05:25:03.010 step: 2
05:25:03.010 - Verify that no link layer frames are received within 2000 ms
05:25:05.012 frame receive timeout
05:25:05.012 step: 3
05:25:05.012 - For a DUT without analog outputs, this section ends here
05:25:05.012 step: 4
05:25:05.012 - Check that analog control point 0 operate
05:25:05.012 [PLG] Analog output 0 did operate
05:25:05.012 Passed procedure: 8.4.3.2.1