8.6.4a Test Procedure for Devices with Global Remote Supervisory Control (revision 3.1r1, subset level 3)

Device under test: Step Function I/O dnp3 outstation

05:25:34.457 Running procedure: 8.6.4a
05:25:34.463 This procedure is enabled because the following options:
05:25:34.463 - supports.globalRemoteSupervisoryControl == true
05:25:34.463 - supports.binaryOutput.status == true
05:25:34.463 - supports.binaryOutput.commands == true
05:25:34.463 step: 1.1
05:25:34.463 - Set the DUT's remote supervisory control to 'Enabled' or 'Remote', globally and for every point
05:25:34.465 [PLG] Every binary output is under remote control
05:25:34.465 step: 1.2
05:25:34.465 - Binary output 0, the one the controls go to, must be online and have no exception flags
05:25:34.466 step: 1.3
05:25:34.466 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:34.466 - g10v0, All Objects
05:25:34.466 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
05:25:34.466 g10v0, All Objects
05:25:34.466 --T-> fir: 1 fin: 1 seq: 0
05:25:34.466 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
05:25:34.466 --P-> 05 64 0B C4 00 04 01 00 CA 8A
05:25:34.466 C0 C0 01 0A 00 06 53 98
05:25:34.466 steps: 1.4 to 1.5
05:25:34.466 - Read any number of valid responses beginning w/ sequence(0x00) and incrementing by 1 modulo 16
05:25:34.466 - Verify that the response contains objects
05:25:34.466 - Verify that the device responds with only variations: Set(g10v1, g10v2)
05:25:34.466 - Verify that the objects are in start/stop ranges with 1-octet (qualifier 0x00) or 2-octet (qualifier 0x01) indexes
05:25:34.466 - Verify that the IIN field does not contain bits IIN(LocalControl)
05:25:34.466 - Verify that each fragment followed by another, or carrying events, asks for an application layer confirmation.
05:25:34.466 - Note each binary output's flags, to compare the later reads with
05:25:34.466 - Verify that binary output(s) 0 are online, with no exception flags
05:25:34.466 - Confirm each response that asks for a confirmation
05:25:34.467 <-P-- 05 64 25 44 01 00 00 04 07 3D
05:25:34.467 C0 C0 81 90 00 0A 02 01 00 00 13 00 01 01 01 01 3A 43
05:25:34.467 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 BB C3
05:25:34.467 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 37 dest: 1 src: 1024
05:25:34.467 <-T-- fir: 1 fin: 1 seq: 0
05:25:34.467 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
05:25:34.467 g10v2, 2-Byte Start/Stop, start: 0 stop: 19
05:25:34.467 [0] - flags: 0x01
05:25:34.467 [1] - flags: 0x01
05:25:34.467 [2] - flags: 0x01
05:25:34.467 [3] - flags: 0x01
05:25:34.467 [4] - flags: 0x01
05:25:34.467 [5] - flags: 0x01
05:25:34.467 [6] - flags: 0x01
05:25:34.467 [7] - flags: 0x01
05:25:34.467 [8] - flags: 0x01
05:25:34.467 [9] - flags: 0x01
05:25:34.467 [10] - flags: 0x01
05:25:34.467 [11] - flags: 0x01
05:25:34.467 [12] - flags: 0x01
05:25:34.467 [13] - flags: 0x01
05:25:34.467 [14] - flags: 0x01
05:25:34.467 [15] - flags: 0x01
05:25:34.467 [16] - flags: 0x01
05:25:34.467 [17] - flags: 0x01
05:25:34.467 [18] - flags: 0x01
05:25:34.467 [19] - flags: 0x01
05:25:34.470 step: 1.6
05:25:34.470 - Set the DUT's global remote supervisory switch to 'Disabled' or 'Local'
05:25:34.471 [PLG] Global remote supervisory control was enabled
05:25:34.471 step: 1.7
05:25:34.471 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:25:34.471 - g10v0, All Objects
05:25:34.471 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
05:25:34.471 g10v0, All Objects
05:25:34.471 --T-> fir: 1 fin: 1 seq: 0
05:25:34.471 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
05:25:34.471 --P-> 05 64 0B C4 00 04 01 00 CA 8A
05:25:34.471 C0 C1 01 0A 00 06 55 BB
05:25:34.471 steps: 1.8 to 1.9
05:25:34.471 - Read any number of valid responses beginning w/ sequence(0x01) and incrementing by 1 modulo 16
05:25:34.471 - Verify that the response contains objects
05:25:34.471 - Verify that the device responds with only variations: Set(g10v1, g10v2)
05:25:34.471 - Verify that the objects are in start/stop ranges with 1-octet (qualifier 0x00) or 2-octet (qualifier 0x01) indexes
05:25:34.471 - Verify that the IIN field contains IIN(LocalControl)
05:25:34.471 - Verify that each fragment followed by another, or carrying events, asks for an application layer confirmation.
05:25:34.471 - Verify that each binary output cleared ONLINE, that every binary output kept the state and other flags it had in the first read
05:25:34.471 - Confirm each response that asks for a confirmation
05:25:34.471 <-P-- 05 64 25 44 01 00 00 04 07 3D
05:25:34.471 C1 C1 81 B0 00 0A 02 01 00 00 13 00 00 00 00 00 3F E7
05:25:34.471 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 FF FF
05:25:34.471 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 37 dest: 1 src: 1024
05:25:34.471 <-T-- fir: 1 fin: 1 seq: 1
05:25:34.471 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, LocalControl, NeedTime)
05:25:34.471 g10v2, 2-Byte Start/Stop, start: 0 stop: 19
05:25:34.471 [0] - flags: 0x00
05:25:34.471 [1] - flags: 0x00
05:25:34.471 [2] - flags: 0x00
05:25:34.471 [3] - flags: 0x00
05:25:34.471 [4] - flags: 0x00
05:25:34.471 [5] - flags: 0x00
05:25:34.471 [6] - flags: 0x00
05:25:34.471 [7] - flags: 0x00
05:25:34.471 [8] - flags: 0x00
05:25:34.471 [9] - flags: 0x00
05:25:34.471 [10] - flags: 0x00
05:25:34.471 [11] - flags: 0x00
05:25:34.471 [12] - flags: 0x00
05:25:34.471 [13] - flags: 0x00
05:25:34.471 [14] - flags: 0x00
05:25:34.471 [15] - flags: 0x00
05:25:34.471 [16] - flags: 0x00
05:25:34.471 [17] - flags: 0x00
05:25:34.471 [18] - flags: 0x00
05:25:34.471 [19] - flags: 0x00
05:25:34.473 step: 1.10
05:25:34.473 - Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
05:25:34.473 - g12v1, 1-Byte Count and Index, count: 1
05:25:34.473 - [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
05:25:34.473 --A-> Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
05:25:34.473 g12v1, 1-Byte Count and Index, count: 1
05:25:34.473 [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
05:25:34.473 --T-> fir: 1 fin: 1 seq: 0
05:25:34.473 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 24 dest: 1024 src: 1
05:25:34.473 --P-> 05 64 18 C4 00 04 01 00 5B 61
05:25:34.473 C0 C2 05 0C 01 17 01 00 03 01 64 00 00 00 C8 00 ED 4B
05:25:34.473 00 00 00 FF FF
05:25:34.473 step: 1.11
05:25:34.473 - Read a single fragment response w/ sequence(0x02)
05:25:34.473 - Verify the response contains the exact object header:
05:25:34.473 - g12v1, 1-Byte Count and Index, count: 1
05:25:34.473 - [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 7 (LOCAL)
05:25:34.473 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
05:25:34.473 - Verify that the IIN field contains IIN(LocalControl)
05:25:34.473 <-P-- 05 64 1A 44 01 00 00 04 A6 F0
05:25:34.473 C2 C2 81 B0 00 0C 01 17 01 00 03 01 64 00 00 00 65 1C
05:25:34.473 C8 00 00 00 07 E2 78
05:25:34.473 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 26 dest: 1 src: 1024
05:25:34.473 <-T-- fir: 1 fin: 1 seq: 2
05:25:34.474 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02 IIN(DeviceRestart, LocalControl, NeedTime)
05:25:34.474 g12v1, 1-Byte Count and Index, count: 1
05:25:34.474 [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 7 (LOCAL)
05:25:34.474 step: 1.12
05:25:34.474 - Check that no binary control point operated
05:25:35.475 [PLG] Binary output did NOT operate
05:25:35.475 step: 1.13
05:25:35.475 - Set the DUT's remote supervisory control to 'Enabled' or 'Remote', globally and for every point
05:25:35.475 [PLG] Every binary output is under remote control
05:25:35.475 step: 1.14
05:25:35.475 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x03
05:25:35.475 - g10v0, All Objects
05:25:35.475 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x03
05:25:35.475 g10v0, All Objects
05:25:35.475 --T-> fir: 1 fin: 1 seq: 0
05:25:35.475 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
05:25:35.475 --P-> 05 64 0B C4 00 04 01 00 CA 8A
05:25:35.475 C0 C3 01 0A 00 06 59 FD
05:25:35.476 step: 1.15
05:25:35.476 - Read any number of valid responses beginning w/ sequence(0x03) and incrementing by 1 modulo 16
05:25:35.476 - Verify that the response contains objects
05:25:35.476 - Verify that the device responds with only variations: Set(g10v1, g10v2)
05:25:35.476 - Verify that the objects are in start/stop ranges with 1-octet (qualifier 0x00) or 2-octet (qualifier 0x01) indexes
05:25:35.476 - Verify that the IIN field does not contain bits IIN(LocalControl)
05:25:35.476 - Verify that each fragment followed by another, or carrying events, asks for an application layer confirmation.
05:25:35.476 - Verify that every binary output has the flags it had in the first read
05:25:35.476 - Confirm each response that asks for a confirmation
05:25:35.476 <-P-- 05 64 25 44 01 00 00 04 07 3D
05:25:35.476 C3 C3 81 90 00 0A 02 01 00 00 13 00 01 01 01 01 86 27
05:25:35.476 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 BB C3
05:25:35.476 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 37 dest: 1 src: 1024
05:25:35.476 <-T-- fir: 1 fin: 1 seq: 3
05:25:35.476 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x03 IIN(DeviceRestart, NeedTime)
05:25:35.476 g10v2, 2-Byte Start/Stop, start: 0 stop: 19
05:25:35.476 [0] - flags: 0x01
05:25:35.476 [1] - flags: 0x01
05:25:35.476 [2] - flags: 0x01
05:25:35.476 [3] - flags: 0x01
05:25:35.476 [4] - flags: 0x01
05:25:35.476 [5] - flags: 0x01
05:25:35.476 [6] - flags: 0x01
05:25:35.476 [7] - flags: 0x01
05:25:35.476 [8] - flags: 0x01
05:25:35.476 [9] - flags: 0x01
05:25:35.476 [10] - flags: 0x01
05:25:35.476 [11] - flags: 0x01
05:25:35.476 [12] - flags: 0x01
05:25:35.476 [13] - flags: 0x01
05:25:35.476 [14] - flags: 0x01
05:25:35.476 [15] - flags: 0x01
05:25:35.476 [16] - flags: 0x01
05:25:35.476 [17] - flags: 0x01
05:25:35.476 [18] - flags: 0x01
05:25:35.476 [19] - flags: 0x01
05:25:35.479 step: 1.16
05:25:35.479 - Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x04
05:25:35.479 - g12v1, 1-Byte Count and Index, count: 1
05:25:35.479 - [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
05:25:35.479 --A-> Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x04
05:25:35.479 g12v1, 1-Byte Count and Index, count: 1
05:25:35.479 [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
05:25:35.479 --T-> fir: 1 fin: 1 seq: 0
05:25:35.479 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 24 dest: 1024 src: 1
05:25:35.479 --P-> 05 64 18 C4 00 04 01 00 5B 61
05:25:35.479 C0 C4 05 0C 01 17 01 00 03 01 64 00 00 00 C8 00 C4 62
05:25:35.479 00 00 00 FF FF
05:25:35.480 step: 1.17
05:25:35.480 - Read a single fragment response w/ sequence(0x04)
05:25:35.480 - Verify the response contains the exact object header:
05:25:35.480 - g12v1, 1-Byte Count and Index, count: 1
05:25:35.480 - [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
05:25:35.480 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
05:25:35.480 - Verify that the IIN field does not contain bits IIN(LocalControl)
05:25:35.483 <-P-- 05 64 1A 44 01 00 00 04 A6 F0
05:25:35.483 C4 C4 81 90 00 0C 01 17 01 00 03 01 64 00 00 00 CC 14
05:25:35.483 C8 00 00 00 00 78 FB
05:25:35.483 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 26 dest: 1 src: 1024
05:25:35.483 <-T-- fir: 1 fin: 1 seq: 4
05:25:35.483 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x04 IIN(DeviceRestart, NeedTime)
05:25:35.483 g12v1, 1-Byte Count and Index, count: 1
05:25:35.483 [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
05:25:35.483 step: 1.18
05:25:35.483 - Check that binary control point 0 operate
05:25:35.483 [PLG] Binary output 0 did operate
05:25:35.483 Passed procedure: 8.6.4a