8.13.2.3 Device supports Binary Inputs, Configurable Device (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

10:59:37.853 Running procedure: 8.13.2.3
10:59:37.854 This procedure is enabled because the following options:
10:59:37.854 - supports.binaryInput == true
10:59:37.854 - supports.disable.binaryInput == true
10:59:37.854 step: 1
10:59:37.854 - The DUT's binary inputs can be uninstalled or disabled through its configuration
10:59:37.854 step: 2
10:59:37.854 - Uninstall or disable every binary input point on the DUT
10:59:37.854 [PLG] All binary input points were uninstalled
10:59:37.854 [PLG] Cycling power
10:59:37.854 step: 3
10:59:37.854 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
10:59:37.854 - g1v0, All Objects
10:59:37.855 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
10:59:37.855 g1v0, All Objects
10:59:37.855 --T-> fir: 1 fin: 1 seq: 0
10:59:37.855 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
10:59:37.855 --P-> 05 64 0B C4 00 04 01 00 CA 8A
10:59:37.855 C0 C1 01 01 00 06 5D 5C
10:59:37.855 step: 4
10:59:37.855 - Read a single fragment response w/ sequence(0x01)
10:59:37.855 - Verify that the response is a Null Response, or an Error Response whose only error bits are IIN(ObjectUnknown)
10:59:37.855 <-P-- 05 64 0A 44 01 00 00 04 67 88
10:59:37.855 C0 C1 81 90 02 CF 82
10:59:37.855 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
10:59:37.855 <-T-- fir: 1 fin: 1 seq: 0
10:59:37.855 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime, ObjectUnknown)
10:59:37.855 Passed procedure: 8.13.2.3
10:59:37.855 restore
10:59:37.855 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
10:59:37.855 [PLG] All points were reinstalled
10:59:37.855 [PLG] Cycling power