8.16.1.2.3 Device supports Binary Counters, Configurable Device (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

11:01:08.497 Running procedure: 8.16.1.2.3
11:01:08.498 This procedure is enabled because the following options:
11:01:08.498 - supports.counter == true
11:01:08.498 - supports.disable.counter == true
11:01:08.498 step: 1
11:01:08.498 - The DUT's counters can be uninstalled or disabled through its configuration
11:01:08.498 step: 2
11:01:08.498 - Uninstall or disable every counter point on the DUT
11:01:08.498 [PLG] All counter points were uninstalled
11:01:08.498 [PLG] Cycling power
11:01:08.498 step: 3
11:01:08.498 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:01:08.498 - g20v0, All Objects
11:01:08.499 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:01:08.499 g20v0, All Objects
11:01:08.499 --T-> fir: 1 fin: 1 seq: 0
11:01:08.499 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
11:01:08.499 --P-> 05 64 0B C4 00 04 01 00 CA 8A
11:01:08.499 C0 C1 01 14 00 06 FC F5
11:01:08.499 step: 4
11:01:08.499 - Read a single fragment response w/ sequence(0x01)
11:01:08.499 - Verify that the response is a Null Response, or an Error Response whose only error bits are IIN(ObjectUnknown)
11:01:08.499 <-P-- 05 64 0A 44 01 00 00 04 67 88
11:01:08.499 C0 C1 81 90 02 CF 82
11:01:08.500 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
11:01:08.500 <-T-- fir: 1 fin: 1 seq: 0
11:01:08.500 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime, ObjectUnknown)
11:01:08.500 Passed procedure: 8.16.1.2.3
11:01:08.500 restore
11:01:08.500 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
11:01:08.500 [PLG] All points were reinstalled
11:01:08.500 [PLG] Cycling power