8.2.1.2.10 Binary Output, SBO, Configurable Device (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

10:56:11.491 Running procedure: 8.2.1.2.10
10:56:11.493 This procedure is enabled because the following options:
10:56:11.493 - supports.binaryOutput.commands == true
10:56:11.493 - supports.disable.binaryOutput == true
10:56:11.493 step: 1
10:56:11.493 - The DUT's binary outputs can be uninstalled or disabled through its configuration
10:56:11.493 step: 2
10:56:11.493 - Uninstall or disable every binary output point on the DUT
10:56:11.494 [PLG] All binary output status points were uninstalled
10:56:11.494 [PLG] Cycling power
10:56:11.495 step: 3
10:56:11.495 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:11.495 - g12v1, 2-Byte Count and Index, count: 1
10:56:11.495 - [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
10:56:11.495 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:11.495 g12v1, 2-Byte Count and Index, count: 1
10:56:11.495 [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
10:56:11.495 --T-> fir: 1 fin: 1 seq: 0
10:56:11.495 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 26 dest: 1024 src: 1
10:56:11.495 --P-> 05 64 1A C4 00 04 01 00 EC 47
10:56:11.495 C0 C0 03 0C 01 28 01 00 00 00 03 01 64 00 00 00 FD 6B
10:56:11.495 C8 00 00 00 00 78 FB
10:56:11.496 step: 4
10:56:11.496 - Read a single fragment response w/ sequence(0x00)
10:56:11.496 - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown)
10:56:11.497 <-P-- 05 64 1C 44 01 00 00 04 7F 9B
10:56:11.497 C0 C0 81 90 04 0C 01 28 01 00 00 00 03 01 64 00 1E 04
10:56:11.497 00 00 C8 00 00 00 04 00 22
10:56:11.497 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 28 dest: 1 src: 1024
10:56:11.497 <-T-- fir: 1 fin: 1 seq: 0
10:56:11.498 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime, ParamError)
10:56:11.498 g12v1, 2-Byte Count and Index, count: 1
10:56:11.498 [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 4 (NOT_SUPPORTED)
10:56:11.498 step: 5
10:56:11.498 - Check that no binary control point operated
10:56:12.499 [PLG] Binary output did NOT operate
10:56:12.499 Passed procedure: 8.2.1.2.10
10:56:12.499 restore
10:56:12.499 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
10:56:12.499 [PLG] All points were reinstalled
10:56:12.499 [PLG] Cycling power