8.2.1.2.3 Binary Output, SBO, To Uninstalled Point (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

10:55:59.762 Running procedure: 8.2.1.2.3
10:55:59.764 This procedure is enabled because the following options:
10:55:59.764 - supports.binaryOutput.commands == true
10:55:59.764 step: 1
10:55:59.764 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:55:59.764 - g12v1, 2-Byte Count and Index, count: 1
10:55:59.764 - [65535] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
10:55:59.765 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:55:59.765 g12v1, 2-Byte Count and Index, count: 1
10:55:59.765 [65535] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
10:55:59.765 --T-> fir: 1 fin: 1 seq: 0
10:55:59.765 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 26 dest: 1024 src: 1
10:55:59.765 --P-> 05 64 1A C4 00 04 01 00 EC 47
10:55:59.765 C0 C0 03 0C 01 28 01 00 FF FF 03 01 64 00 00 00 79 CE
10:55:59.765 C8 00 00 00 00 78 FB
10:55:59.765 step: 2
10:55:59.765 - Read a single fragment response w/ sequence(0x00)
10:55:59.765 - Verify that the IIN field contains IIN(ParamError)
10:55:59.765 - Verify the response contains the exact object header:
10:55:59.765 - g12v1, 2-Byte Count and Index, count: 1
10:55:59.765 - [65535] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 4 (NOT_SUPPORTED)
10:55:59.765 <-P-- 05 64 1C 44 01 00 00 04 7F 9B
10:55:59.765 C0 C0 81 90 04 0C 01 28 01 00 FF FF 03 01 64 00 1B 29
10:55:59.765 00 00 C8 00 00 00 04 00 22
10:55:59.765 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 28 dest: 1 src: 1024
10:55:59.765 <-T-- fir: 1 fin: 1 seq: 0
10:55:59.766 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime, ParamError)
10:55:59.766 g12v1, 2-Byte Count and Index, count: 1
10:55:59.766 [65535] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 4 (NOT_SUPPORTED)
10:55:59.766 step: 3
10:55:59.766 - Check that no binary control point operated
10:56:00.767 [PLG] Binary output did NOT operate
10:56:00.767 Passed procedure: 8.2.1.2.3