8.2.3.2.2 Binary Output, Direct Operate, No Acknowledge, to an Uninstalled Point (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

10:56:22.898 Running procedure: 8.2.3.2.2
10:56:22.899 This procedure is enabled because the following options:
10:56:22.899 - supports.binaryOutput.commands == true
10:56:22.899 step: 1
10:56:22.899 - Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:22.899 - g12v1, 2-Byte Count and Index, count: 1
10:56:22.899 - [65535] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
10:56:22.899 --A-> Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:22.899 g12v1, 2-Byte Count and Index, count: 1
10:56:22.899 [65535] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
10:56:22.899 --T-> fir: 1 fin: 1 seq: 0
10:56:22.899 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 26 dest: 1024 src: 1
10:56:22.900 --P-> 05 64 1A C4 00 04 01 00 EC 47
10:56:22.900 C0 C0 06 0C 01 28 01 00 FF FF 03 01 64 00 00 00 49 0B
10:56:22.900 C8 00 00 00 00 78 FB
10:56:22.900 step: 2
10:56:22.900 - Verify that no link layer frames are received within 2000 ms
10:56:24.901 frame receive timeout
10:56:24.901 step: 3
10:56:24.901 - Check that no binary control point operated
10:56:25.903 [PLG] Binary output did NOT operate
10:56:25.903 Passed procedure: 8.2.3.2.2