8.21.2.2 Device supports Double-bit Inputs, Configurable Device (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

11:01:33.937 Running procedure: 8.21.2.2
11:01:33.938 This procedure is enabled because the following options:
11:01:33.938 - supports.doubleBitInput == true
11:01:33.938 - supports.disable.doubleBitInput == true
11:01:33.938 step: 1
11:01:33.938 - The DUT's double-bit inputs can be uninstalled or disabled through its configuration
11:01:33.938 step: 2
11:01:33.938 - Uninstall or disable every double-bit binary input point on the DUT
11:01:33.938 [PLG] All double-bit binary input points were uninstalled
11:01:33.938 [PLG] Cycling power
11:01:33.938 step: 3
11:01:33.938 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
11:01:33.938 - g3v0, All Objects
11:01:33.939 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
11:01:33.939 g3v0, All Objects
11:01:33.939 --T-> fir: 1 fin: 1 seq: 0
11:01:33.939 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
11:01:33.939 --P-> 05 64 0B C4 00 04 01 00 CA 8A
11:01:33.939 C0 C0 01 03 00 06 2B 4C
11:01:33.939 step: 4
11:01:33.939 - Read a single fragment response w/ sequence(0x00)
11:01:33.939 - Verify that the response is a Null Response, or an Error Response whose only error bits are IIN(ObjectUnknown)
11:01:33.939 <-P-- 05 64 0A 44 01 00 00 04 67 88
11:01:33.939 C0 C0 81 90 02 27 40
11:01:33.939 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
11:01:33.939 <-T-- fir: 1 fin: 1 seq: 0
11:01:33.939 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime, ObjectUnknown)
11:01:33.939 Passed procedure: 8.21.2.2
11:01:33.939 restore
11:01:33.939 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
11:01:33.939 [PLG] All points were reinstalled
11:01:33.939 [PLG] Cycling power