8.4.1.2.5 Analog Output, SBO, Execute Value does not match Select Value (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

10:56:36.350 Running procedure: 8.4.1.2.5
10:56:36.351 This procedure is enabled because the following options:
10:56:36.351 - supports.analogOutput.commands == true
10:56:36.352 step: 1
10:56:36.352 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:36.352 - g41v2, 1-Byte Count and Index, count: 1
10:56:36.352 - [0] - value: 10 status: 0 (SUCCESS)
10:56:36.352 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:36.352 g41v2, 1-Byte Count and Index, count: 1
10:56:36.352 [0] - value: 10 status: 0 (SUCCESS)
10:56:36.352 --T-> fir: 1 fin: 1 seq: 0
10:56:36.352 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 16 dest: 1024 src: 1
10:56:36.352 --P-> 05 64 10 C4 00 04 01 00 87 FB
10:56:36.352 C0 C0 03 29 02 17 01 00 0A 00 00 9F B0
10:56:36.353 step: 2
10:56:36.353 - Read a single fragment response w/ sequence(0x00)
10:56:36.353 - Verify the response contains the exact object header:
10:56:36.353 - g41v2, 1-Byte Count and Index, count: 1
10:56:36.353 - [0] - value: 10 status: 0 (SUCCESS)
10:56:36.353 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
10:56:36.353 <-P-- 05 64 12 44 01 00 00 04 7A 6A
10:56:36.353 C0 C0 81 90 00 29 02 17 01 00 0A 00 00 6A 73
10:56:36.353 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 18 dest: 1 src: 1024
10:56:36.353 <-T-- fir: 1 fin: 1 seq: 0
10:56:36.354 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
10:56:36.354 g41v2, 1-Byte Count and Index, count: 1
10:56:36.354 [0] - value: 10 status: 0 (SUCCESS)
10:56:36.354 step: 3
10:56:36.354 - Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
10:56:36.354 - g41v2, 1-Byte Count and Index, count: 1
10:56:36.354 - [0] - value: 11 status: 0 (SUCCESS)
10:56:36.354 --A-> Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
10:56:36.354 g41v2, 1-Byte Count and Index, count: 1
10:56:36.354 [0] - value: 11 status: 0 (SUCCESS)
10:56:36.354 --T-> fir: 1 fin: 1 seq: 0
10:56:36.354 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 16 dest: 1024 src: 1
10:56:36.354 --P-> 05 64 10 C4 00 04 01 00 87 FB
10:56:36.354 C0 C1 04 29 02 17 01 00 0B 00 00 F0 E8
10:56:36.354 step: 4
10:56:36.354 - Read a single fragment response w/ sequence(0x01)
10:56:36.354 - Verify the response contains the exact object header:
10:56:36.354 - g41v2, 1-Byte Count and Index, count: 1
10:56:36.354 - [0] - value: 11 status: 2 (NO_SELECT)
10:56:36.355 <-P-- 05 64 12 44 01 00 00 04 7A 6A
10:56:36.355 C1 C1 81 90 00 29 02 17 01 00 0B 00 02 B2 B5
10:56:36.355 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 18 dest: 1 src: 1024
10:56:36.355 <-T-- fir: 1 fin: 1 seq: 1
10:56:36.355 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime)
10:56:36.355 g41v2, 1-Byte Count and Index, count: 1
10:56:36.355 [0] - value: 11 status: 2 (NO_SELECT)
10:56:36.355 step: 5
10:56:36.355 - Check that no analog control point operated
10:56:37.357 [PLG] Analog output did NOT operate
10:56:37.357 Passed procedure: 8.4.1.2.5