8.4.2.2.2 Analog Output, Direct Operate, to Uninstalled Point (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

10:56:45.509 Running procedure: 8.4.2.2.2
10:56:45.510 This procedure is enabled because the following options:
10:56:45.510 - supports.analogOutput.commands == true
10:56:45.510 step: 1
10:56:45.510 - Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:45.510 - g41v2, 2-Byte Count and Index, count: 1
10:56:45.510 - [65535] - value: 10 status: 0 (SUCCESS)
10:56:45.510 --A-> Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:45.510 g41v2, 2-Byte Count and Index, count: 1
10:56:45.510 [65535] - value: 10 status: 0 (SUCCESS)
10:56:45.510 --T-> fir: 1 fin: 1 seq: 0
10:56:45.510 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 18 dest: 1024 src: 1
10:56:45.510 --P-> 05 64 12 C4 00 04 01 00 30 DD
10:56:45.510 C0 C0 05 29 02 28 01 00 FF FF 0A 00 00 D9 66
10:56:45.510 step: 2
10:56:45.510 - Read a single fragment response w/ sequence(0x00)
10:56:45.510 - Verify that the IIN field contains IIN(ParamError)
10:56:45.510 - Verify the response contains the exact object header:
10:56:45.510 - g41v2, 2-Byte Count and Index, count: 1
10:56:45.510 - [65535] - value: 10 status: 4 (NOT_SUPPORTED)
10:56:45.511 <-P-- 05 64 14 44 01 00 00 04 A3 01
10:56:45.511 C0 C0 81 90 04 29 02 28 01 00 FF FF 0A 00 04 3C 3D
10:56:45.511 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 20 dest: 1 src: 1024
10:56:45.511 <-T-- fir: 1 fin: 1 seq: 0
10:56:45.511 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime, ParamError)
10:56:45.511 g41v2, 2-Byte Count and Index, count: 1
10:56:45.511 [65535] - value: 10 status: 4 (NOT_SUPPORTED)
10:56:45.511 step: 3
10:56:45.511 - Check that no analog control point operated
10:56:46.512 [PLG] Analog output did NOT operate
10:56:46.512 Passed procedure: 8.4.2.2.2