8.4.2.2.3 Analog Output, Direct Operate, Configurable Device (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

10:56:46.751 Running procedure: 8.4.2.2.3
10:56:46.752 This procedure is enabled because the following options:
10:56:46.752 - supports.analogOutput.commands == true
10:56:46.752 - supports.disable.analogOutput == true
10:56:46.752 step: 1
10:56:46.752 - The DUT's analog outputs can be uninstalled or disabled through its configuration
10:56:46.752 step: 2
10:56:46.752 - Uninstall or disable every analog output point on the DUT
10:56:46.752 [PLG] All analog output status points were uninstalled
10:56:46.752 [PLG] Cycling power
10:56:46.752 step: 3
10:56:46.752 - Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:46.752 - g41v2, 2-Byte Count and Index, count: 1
10:56:46.752 - [0] - value: 10 status: 0 (SUCCESS)
10:56:46.753 --A-> Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:46.753 g41v2, 2-Byte Count and Index, count: 1
10:56:46.753 [0] - value: 10 status: 0 (SUCCESS)
10:56:46.753 --T-> fir: 1 fin: 1 seq: 0
10:56:46.753 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 18 dest: 1024 src: 1
10:56:46.753 --P-> 05 64 12 C4 00 04 01 00 30 DD
10:56:46.753 C0 C0 05 29 02 28 01 00 00 00 0A 00 00 64 B4
10:56:46.753 step: 4
10:56:46.753 - Read a single fragment response w/ sequence(0x00)
10:56:46.753 - Verify that the IIN field contains at least one of IIN(ParamError, ObjectUnknown)
10:56:46.754 <-P-- 05 64 14 44 01 00 00 04 A3 01
10:56:46.754 C0 C0 81 90 04 29 02 28 01 00 00 00 0A 00 04 81 EF
10:56:46.754 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 20 dest: 1 src: 1024
10:56:46.754 <-T-- fir: 1 fin: 1 seq: 0
10:56:46.754 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime, ParamError)
10:56:46.754 g41v2, 2-Byte Count and Index, count: 1
10:56:46.754 [0] - value: 10 status: 4 (NOT_SUPPORTED)
10:56:46.755 step: 5
10:56:46.755 - Check that no analog control point operated
10:56:47.756 [PLG] Analog output did NOT operate
10:56:47.756 Passed procedure: 8.4.2.2.3
10:56:47.756 restore
10:56:47.756 - Reinstall or re-enable the points that were uninstalled or disabled, so later procedures can use them
10:56:47.756 [PLG] All points were reinstalled
10:56:47.756 [PLG] Cycling power