8.4.3.2.1 Analog Output, Direct Operate, No Acknowledge (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

10:56:48.001 Running procedure: 8.4.3.2.1
10:56:48.002 step: 1
10:56:48.002 - Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:48.002 - g41v2, 1-Byte Count and Index, count: 1
10:56:48.002 - [0] - value: 10 status: 0 (SUCCESS)
10:56:48.002 --A-> Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:48.002 g41v2, 1-Byte Count and Index, count: 1
10:56:48.002 [0] - value: 10 status: 0 (SUCCESS)
10:56:48.002 --T-> fir: 1 fin: 1 seq: 0
10:56:48.002 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 16 dest: 1024 src: 1
10:56:48.002 --P-> 05 64 10 C4 00 04 01 00 87 FB
10:56:48.002 C0 C0 06 29 02 17 01 00 0A 00 00 D1 C2
10:56:48.002 step: 2
10:56:48.002 - Verify that no link layer frames are received within 2000 ms
10:56:50.005 frame receive timeout
10:56:50.005 step: 3
10:56:50.005 - For a DUT without analog outputs, this section ends here
10:56:50.005 step: 4
10:56:50.005 - Check that analog control point 0 operate
10:56:50.005 [PLG] Analog output 0 did operate
10:56:50.005 Passed procedure: 8.4.3.2.1