8.4.3.2.2 Analog Output, Direct Operate, No Acknowledge, to an Uninstalled Point (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

10:56:50.233 Running procedure: 8.4.3.2.2
10:56:50.233 This procedure is enabled because the following options:
10:56:50.233 - supports.analogOutput.commands == true
10:56:50.234 step: 1
10:56:50.234 - Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:50.234 - g41v2, 2-Byte Count and Index, count: 1
10:56:50.234 - [65535] - value: 10 status: 0 (SUCCESS)
10:56:50.234 --A-> Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:56:50.234 g41v2, 2-Byte Count and Index, count: 1
10:56:50.234 [65535] - value: 10 status: 0 (SUCCESS)
10:56:50.234 --T-> fir: 1 fin: 1 seq: 0
10:56:50.234 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 18 dest: 1024 src: 1
10:56:50.234 --P-> 05 64 12 C4 00 04 01 00 30 DD
10:56:50.234 C0 C0 06 29 02 28 01 00 FF FF 0A 00 00 4B 5D
10:56:50.234 step: 2
10:56:50.234 - Verify that no link layer frames are received within 2000 ms
10:56:52.236 frame receive timeout
10:56:52.236 step: 3
10:56:52.236 - Check that no analog control point operated
10:56:53.237 [PLG] Analog output did NOT operate
10:56:53.237 Passed procedure: 8.4.3.2.2