8.6.5.3 Test Procedure (revision 2.7, subset level 2)

Device under test: Step Function I/O dnp3 outstation

10:57:24.386 Running procedure: 8.6.5.3
10:57:24.387 This procedure is enabled because the following options:
10:57:24.387 - supports.binaryOutput.commands == true or supports.analogOutput.commands == true
10:57:24.388 step: 1
10:57:24.388 - Tell a manual tester: Watch binary output 0: it should operate once after the broadcast in step 1. You'll be asked what you saw after the steps. Get ready, then press ENTER.
10:57:24.388 - Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 using link options: { destination == 0xFFFF }
10:57:24.388 - g12v1, 1-Byte Count and Index, count: 1
10:57:24.388 - [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
10:57:24.388 --A-> Direct Operate No Ack(0x06) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
10:57:24.388 g12v1, 1-Byte Count and Index, count: 1
10:57:24.388 [0] - code: 0x03 (LATCH_ON, NUL) count: 1 onTime: 100 offTime: 200 status: 0 (SUCCESS)
10:57:24.388 --T-> fir: 1 fin: 1 seq: 0
10:57:24.388 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 24 dest: 65535 src: 1
10:57:24.388 --P-> 05 64 18 C4 FF FF 01 00 0E E4
10:57:24.388 C0 C0 06 0C 01 17 01 00 03 01 64 00 00 00 C8 00 CD D4
10:57:24.388 00 00 00 FF FF
10:57:24.388 step: 2
10:57:24.388 - Check that binary control point 0 operate
10:57:24.388 [PLG] Binary output 0 did operate
10:57:24.388 steps: 3 to 4
10:57:24.388 - Verify that no link layer frames are received within 2000 ms
10:57:26.389 frame receive timeout
10:57:26.389 step: 5
10:57:26.389 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
10:57:26.389 - g60v2, All Objects
10:57:26.389 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
10:57:26.389 g60v2, All Objects
10:57:26.389 --T-> fir: 1 fin: 1 seq: 0
10:57:26.389 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
10:57:26.390 --P-> 05 64 0B C4 00 04 01 00 CA 8A
10:57:26.390 C0 C2 01 3C 02 06 58 A6
10:57:26.390 steps: 6 to 7
10:57:26.390 - Read any number of valid responses beginning w/ sequence(0x02) and incrementing by 1 modulo 16
10:57:26.390 - Verify that each fragment followed by another, or carrying events, asks for an application layer confirmation.
10:57:26.390 - Verify that the IIN field contains IIN(Broadcast)
10:57:26.390 - Confirm each response that asks for a confirmation
10:57:26.390 <-P-- 05 64 0A 44 01 00 00 04 67 88
10:57:26.390 C0 C2 81 91 00 7C 4F
10:57:26.390 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
10:57:26.390 <-T-- fir: 1 fin: 1 seq: 0
10:57:26.390 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02 IIN(DeviceRestart, NeedTime, Broadcast)
10:57:26.390 step: 8
10:57:26.390 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x03
10:57:26.390 - g60v2, All Objects
10:57:26.390 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x03
10:57:26.390 g60v2, All Objects
10:57:26.390 --T-> fir: 1 fin: 1 seq: 0
10:57:26.390 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
10:57:26.390 --P-> 05 64 0B C4 00 04 01 00 CA 8A
10:57:26.390 C0 C3 01 3C 02 06 5E 85
10:57:26.390 step: 9
10:57:26.390 - Read a single fragment response w/ sequence(0x03)
10:57:26.390 - Verify that the response is empty
10:57:26.390 - Verify that the IIN field does not contain bits IIN(ParamError, ObjectUnknown, FuncNotSupported)
10:57:26.390 - Verify that the IIN field does not contain bits IIN(Broadcast)
10:57:26.391 <-P-- 05 64 0A 44 01 00 00 04 67 88
10:57:26.391 C1 C3 81 90 00 DC 05
10:57:26.391 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
10:57:26.391 <-T-- fir: 1 fin: 1 seq: 1
10:57:26.391 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x03 IIN(DeviceRestart, NeedTime)
10:57:26.391 Passed procedure: 8.6.5.3